Final | 4/6/2011 | 4/6/2011 | 4/6/2011 | P | PASS |
Bob Reichert
|
|
|
justin - late afternoon please Phone #: ###-#### ok final, signed card
|
Electrical Rough-In | 3/18/2011 | 3/21/2011 | 3/21/2011 | A | PASS |
Bob Reichert
|
|
|
Justin please call on your way so he can be there to let you in. Phone #: ###-#### corrections made, ri ok walls and ceilings
|
Electrical Rough-In | 3/18/2011 | 3/18/2011 | 3/18/2011 | P | NR |
Jack Frank
|
|
|
justin - please call 1/2 hr prior so he can meet you there Phone #: ###-#### contr. will request when ready
|
Electrical Rough-In | 3/16/2011 | 3/17/2011 | 3/17/2011 | A | FAIL |
Bob Reichert
|
|
|
justin - please call for access Phone #: ###-#### met contractor, left correction notice, NEC 300.4(D) edge of cable shall be 1 1/4" from edge of framing member, 330.30(A) shall strap mc within 12" of ternination, BCC shall not wire in valley of 2x4, shall close breaker opening and boxes, no lv wiring on grid in ceiling, no violations shall be retained
|
Application received | | | 3/16/2011 | | |
|
|
|
|
Issue permit | | | 3/16/2011 | | DONE |
|
|
|
|
First Notice | 4/6/2011 | 4/6/2011 | | | |
Bob Reichert
|
|
|
|