First Notice | 7/28/2014 | 7/28/2014 | 9/9/2014 | | DONE |
Rock A. Hudson
|
|
|
This permit finaled on the web by kendall bender
|
Final | 7/25/2014 | 7/28/2014 | 7/28/2014 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### >> Inspection requested via web by kendall bender Final ok
|
Final | 7/25/2014 | 7/25/2014 | 7/25/2014 | P | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### >> Inspection requested via web by kendall bender 210.8- All 15 and 20 amp 120 volt receptical outlets shall have GFCI protection. 110.26- Minimum work space of 30" wide and 36" deep shall beclear of vegetation in front of meter panel combo. 314.17- NM cable sheathing shall enter box by minimum of 1/4". Bay 4 opener outlet. 408-4- Circuit directory shall be complete.
|
Electrical Rough-In | 2/12/2014 | 2/12/2014 | 2/12/2014 | P | PASS |
Daryl DeGrange
|
|
|
Phone #: ###-#### >> Inspection requested via web by kendall bender Rough-in ok cover 5 bay garage
|
Electrical Rough-In | 11/12/2013 | 11/12/2013 | 11/12/2013 | P | PASS |
Bob Reichert
|
|
|
Ufer at garage wall Phone #: ###-#### >> Inspection requested via web by kendall bender concrete encased electrode ok cover
|
Issue PAID IN FULL permit | | | 11/12/2013 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 11/12/2013 | | DONE |
|
|
|
This permit was created on the web by kendall bender
|