Final | 7/15/2014 | 7/16/2014 | 7/15/2014 | A | PASS |
Rock A. Hudson
|
|
|
Repaired correction notice about exterior wire. Thank You. Phone #: ###-#### >> Inspection requested via web by Clay Morgan Final ok
|
Final | 7/8/2014 | 7/9/2014 | 7/9/2014 | A | FAIL |
Rock A. Hudson
|
|
|
Lockbox should be 1209/7012, if not, please call Aaron ###-####. Thank You. Phone #: ###-#### >> Inspection requested via web by Clay Morgan 334.12- NM Cable exposed on back patio not rated for exposure to damp location
|
Rough-In Permanent Service | 5/14/2014 | 5/15/2014 | 5/15/2014 | A | PASS |
Rock A. Hudson
|
|
|
Please let me know if there are any problems. Thanks Phone #: ###-#### >> Inspection requested via web by Clay Morgan Rough in ok cover p/s o/h rec ok
|
Rough-In Permanent Service | 5/13/2014 | 5/14/2014 | 5/14/2014 | A | NR |
Bob Reichert
|
|
|
House is open. Phone #: ###-#### >> Inspection requested via web by Clay Morgan called, left message to call back, nm cable over panel shall be secured within 12" of panel, damaged nm in 4 square box, no ground rods installed, no rear receptacle installed, shall seal wiring entering warm area from outside per NEC 300.7
|
Conference | 4/22/2014 | 4/22/2014 | 4/22/2014 | P | DONE |
Rock A. Hudson
|
|
|
Aaron-please call when on your way Phone #: ###-#### Discussed replacing wiring that went to old fuse panel to main service ok enter top of meter main located under covered patio.
|
Issue PAID IN FULL permit | | | 4/21/2014 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 4/21/2014 | | DONE |
|
|
|
This permit was created on the web by Clay Morgan
|