First Notice | 6/25/2014 | 6/25/2014 | 9/11/2014 | | DONE |
Rock A. Hudson
|
|
|
|
Final | 6/25/2014 | 6/25/2014 | 6/25/2014 | A | PASS |
Rock A. Hudson
|
|
|
Wall inspection Phone #: ###-#### >> Inspection requested via web by Charles Davis Needed rough in inspection Walls and hard lid rough in ok cover
|
Electrical Rough-In | 6/23/2014 | 6/24/2014 | 6/24/2014 | A | FAIL |
Bob Reichert
|
|
|
wall cover - Randy Phone #: ###-#### called, left message, left correction notice, NEC300.4(D) shall provide 1 1/4" from edge of framing member to mc cable, 250.86 shall ground metal boxes, BCC shall complete make-up, shall post address
|
Issue PAID IN FULL permit | | | 6/19/2014 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 6/19/2014 | | DONE |
|
|
|
This permit was created on the web by Charles Davis
|