Final | 12/12/2015 | 12/14/2015 | 12/14/2015 | A | PASS |
Rock A. Hudson
|
|
|
Only dining area ; back porch were specifically remodeled due to fire. All else including panel, meter base ; remainder of house are original and untampered with. Added intersystem bonding bridge. Has 2 rods. Call for key code. Phone #: ###-#### Inspection requested via web by David McClellan Final ok
|
Electrical Rough-In | 11/22/2015 | 11/23/2015 | 11/23/2015 | A | PASS |
Rex Boyles
|
|
|
Dining area ; back patio lights. Call for entry code. Phone #: ###-#### Inspection requested via web by David McClellan r/i ok
|
Conference | 10/18/2015 | 10/19/2015 | 10/19/2015 | A | DONE |
Rock A. Hudson
|
|
|
Burn job request consult to determine needs required upgrades if any. Preferably early if possible by 8:30-9 ish Phone #: ###-#### Inspection requested via web by David McClellan Discussed the reconnection of existing service of fire damaged house. Contractor to safe off all damaged circuits and provide power for repair. House rewired in 2001. To remove gas pipe bond, and check for plumbing bond. If plumbing bond exists single ground rod ok. If no plumbing 2nd rod shall be added.
|
Permanent Service | 10/19/2015 | 10/19/2015 | 10/19/2015 | P | PASS |
Rock A. Hudson
|
|
|
Burn job request consult to determine needs required upgrades if any. Preferably early if possible by 8:30-9 ish Phone #: ###-#### Inspection requested via web by David McClellan Contractor to safe off all damaged circuits. p/s u/g rec ok
|
Issue PAID IN FULL permit | | | 10/18/2015 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 10/18/2015 | | DONE |
|
|
|
This permit was created on the web by David McClellan
|