First Notice | 3/9/2018 | 3/9/2018 | 5/23/2018 | | DONE |
Tom Saunders
|
|
|
|
Print Statement | | | 5/23/2018 | | DONE |
|
|
|
|
Final | 3/8/2018 | 3/9/2018 | 3/9/2018 | P | PASS |
Tom Saunders
|
|
|
Danny Phone #: ###-####...ok to final
|
Permanent Service | 3/6/2018 | 3/7/2018 | 3/7/2018 | A | PASS |
Tom Saunders
|
|
|
Danny Phone #: ###-####...p/s u/g new ok
|
Electrical Rough-In | 2/27/2018 | 2/28/2018 | 2/28/2018 | A | PASS |
Daryl DeGrange
|
|
|
Danny-ceiling Phone #: 2###-#### rough-in ok cover ceiling grid
|
Electrical Rough-In | 2/2/2018 | 2/5/2018 | 2/5/2018 | A | PASS |
Tom Saunders
|
|
|
Luke Phone #: ###-####...remaining wall cover ok
|
Electrical Rough-In | 1/31/2018 | 2/1/2018 | 2/1/2018 | A | PASS |
Rock A. Hudson
|
|
|
Luke Phone #: ###-#### Hallway and all walls and hardlids north of hall rough in ok cover
|
Electrical Rough-In | 1/24/2018 | 1/24/2018 | 1/24/2018 | P | PART |
Eric Story
|
|
|
partial r/i // Luke Phone #: ###-#### Corrections fixed, demizing wall only ok to cover
|
Electrical Rough-In | 1/23/2018 | 1/24/2018 | 1/24/2018 | A | FAIL |
Rock A. Hudson
|
|
|
Part for cover- Luke Phone #: ###-#### demizing wall cover only. 300.4- MC cable shall be protected from physical damage where run thru hole that do not maintain 1 1/4" from framing surface. Shallow studs used for demizing wall. Every stud needs a nail plate or remove wiring and reinstall to back wall. 330.30- MC shall be secured with in 12" of a boxes. 5 or 6 locations on demizing wall.
|
Electrical Rough-In | 1/16/2018 | 1/17/2018 | 1/17/2018 | P | PASS |
Tom Saunders
|
|
|
UG insp// Luke Phone #: ###-####...UG for service...ok to cover
|
Issue PAID IN FULL permit | | | 1/16/2018 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 1/16/2018 | | DONE |
|
|
|
This permit was created on the web by Kevin Perez
|