Final | 6/22/2018 | 6/25/2018 | 6/25/2018 | A | PASS |
Tom Saunders
|
|
|
access 2758 Phone #: ###-#### Inspection requested via web by David Nelson...corrections made...ok to final
|
Final | 6/20/2018 | 6/20/2018 | 6/20/2018 | P | FAIL |
Tom Saunders
|
|
|
access 2758 Phone #: ###-#### Inspection requested via web by David Nelson... 1) all outlets serving kitchen counters shall have GFCI protection...210.8(A)...outlet labelled micro in panel 2) boxes set back in combustible material shall extend to finished surface...314.20...dining rm
|
Rough-In Permanent Service | 4/17/2018 | 4/18/2018 | 4/18/2018 | A | PASS |
Tom Saunders
|
|
|
Phone #: ###-#### Inspection requested via web by David Nelson...rough ok to cover...p/s u/g new/reconnect ok
|
Issue PAID IN FULL permit | | | 4/17/2018 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 4/17/2018 | | DONE |
|
|
|
This permit was created on the web by David Nelson
|