INSP-Final Inspection | 6/6/2001 | 6/6/2001 | 6/6/2001 | P | PASS |
Rick Jackson
|
|
|
Added by Inspector: 409 On 6/6/2001 2:35:09 PM
|
DOC - Permit Finaled | 6/6/2001 | 6/6/2001 | 6/6/2001 | P | PASS |
Rick Jackson
|
|
|
Finaled by inspector at 6/6/2001 2:35:14 PM
|
INSP-Sprinkler Rough-in/Hydro | 5/1/2001 | 5/2/2001 | 5/2/2001 | A | PART |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 05/01/2001 at 14:24:52. Contact: ###-####. need FDC location adjusted to maintain 3 foot clearance; above and underground hydro okay 5/2/2001 10:20:56 AM
|
INSP-Sprinkler Rough-in/Hydro | 4/23/2001 | 4/24/2001 | 4/24/2001 | A | FAIL |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 04/23/2001 at 13:08:12. Contact: ###-####. high temp heads at heaters; standard response head in elevator machine room; earthquaking needed in several areas as noted on plans; review notes indicate 155 temp heads - need designer input 4/24/2001 9:34:52 AM
|
INSP-Supply line flush | 4/24/2001 | 4/24/2001 | 4/24/2001 | A | PASS |
Rick Jackson
|
|
|
Added by Inspector: 409 On 4/24/2001 9:33:20 AM
|
INSP-Supply line flush | 4/23/2001 | 4/24/2001 | 4/23/2001 | A | PART |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 04/23/2001 at 11:40:12. Contact: ###-####. cover inspection - okay to cover 4/23/2001 2:00:57 PM
|
INSP-Supply line flush | 4/18/2001 | 4/19/2001 | 4/18/2001 | A | CANC |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 04/18/2001 at 08:35:25. Contact: ###-####. Disp set to [CANC] by a contractor via Hello! on 04/18/2001 at 13:13:46.
|
Issue and Print Permit | | | 3/19/2001 | | DONE |
|
|
|
|
Sprinkler Plan Check | 3/15/2001 | | 3/16/2001 | | PASS |
Bill Alexander
|
|
|
Revised 2nd Floor Sprinkler Plan and Calculations
|
PLANS/APPL TAKEN TO FRONT DESK | | | 3/16/2001 | | DONE |
Bill Alexander
|
|
|
|
Telephone call | | | 3/16/2001 | | DONE |
|
|
|
|
INSP-Conference | 3/6/2001 | 3/6/2001 | 3/6/2001 | P | PART |
Rick Jackson
|
|
|
Paul ###-#### called contractor and he wanted to know if he could rock some hallways as the sprinkler piping will still be viewable - rocking approved 3/6/2001 3:37:48 PM
|
Telephone call | | | 2/26/2001 | | DONE |
|
|
|
left mess that permit is ready
|
Issue permit | | | 2/26/2001 | | DONE |
|
|
|
|
Telephone call | | | 2/23/2001 | | DONE |
Bill Alexander
|
|
|
Copy of review faxed to Treasure Valley Fire.
|
Sprinkler Plan Check | 2/20/2001 | | 2/23/2001 | | PASS |
Bill Alexander
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 2/23/2001 | | DONE |
Bill Alexander
|
|
|
|
Plan assigned to (Bill) | 2/20/2001 | | 2/23/2001 | | DONE |
|
|
|
2/23/2001 13:28:02 JWA - activity updated through activity FIRA22 from case FIR01-00066.
|
Application received | | | 2/20/2001 | | PASS |
Bill Alexander
|
|
|
|
Inspection Record Card- Bld | 2/26/2001 | 2/26/2001 | | | |
|
|
|
|
Case Summary | | | | | DONE |
|
|
|
|
Case Summary | | | | | DONE |
|
|
|
|