DOC - Permit Finaled | 1/30/2002 | 1/30/2002 | 1/30/2002 | P | PASS |
Rick Jackson
|
|
|
Finaled by inspector at 1/30/2002 11:57:19 AM
|
Alarm Plan Check | | | 7/11/2001 | | PASS |
|
|
|
4th submittal; now acceptable, per review done 7/5 by JWA and RJ in SLR's absence. Calc's re-verified, 7/11.
|
Issue permit | | | 7/6/2001 | | DONE |
|
|
|
|
INSP-Final Inspection | 7/5/2001 | 7/5/2001 | 7/5/2001 | P | PART |
Rick Jackson
|
|
|
Added by Inspector: 409 On 7/5/2001 3:21:32 PM existing strobe problems
|
Alarm Plan Check | 7/5/2001 | | 7/5/2001 | | PASS |
Bill Alexander
|
|
|
Must reverify numbers in calculations.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 7/5/2001 | | DONE |
Bill Alexander
|
|
|
|
Telephone call | | | 7/5/2001 | | DONE |
|
|
|
called ###-#### permit ready for pickup
|
Inspection Record Card- Fire | 7/5/2001 | | 7/5/2001 | | DONE |
|
|
|
|
Telephone call | | | 6/27/2001 | | DONE |
|
|
|
call from Jason at Allied: they will fax calc's this afternoon.
|
Alarm Plan Check | 6/27/2001 | | 6/27/2001 | | FAIL |
|
|
|
Battery calc's faxed, still incomplete and erroneous. Called Jason at Allied advised they need to have someone "experienced in the design of fire alarm systems" do the calc's for them and re-submit.
|
Alarm Plan Check | | | 6/26/2001 | | FAIL |
|
|
|
Plans walked in; did desk review; battery calculations incomplete; requested they fax proper calc's.
|
Application received | | | 6/19/2001 | | |
|
|
|
|
Alarm Plan Check | 6/19/2001 | | 6/19/2001 | | FAIL |
|
|
|
Comments discussed with Wayne Cuber, City Electrician, Jim Dorsey Mountain Power electrical contractor, and Jason Wray, Allied Security. Faxed to Allied Security, Mtn Pwr, and Wayne Cuber.
|