Information based on query as of Saturday, September 28, 2024.
Permit Information
Permit NumberFIR02-00151
StatusFinaled
Name ALARMCO
Site Address 5420 W STATE ST
Project Namealm-GEM STATE GYMNASTICS
Customer Number 
ePlanReview 
Description
GEM STATE GYMNASTICS - To modify an existing building fire alarm system to meet the requirements for the new tenant occupancy.The associated building permit (BLD 01-02575) is to CONVERT AN EXISTING, NON SPRINKLERED, WAREHOUSE INTO AN EXERCISE \ DAYCARE AREA AND TO CONVERT AN EXISTING OFFICE SPACE TO DAYCARE WITH OFFICES ABOVE. OTHER WORK INCLUDES A NEW 2HR AREA SEPARATION WALL WHICH IS TO BE CONSTRUCTED IN THE ADJACENT TENANT SPACE IN BUILDING #3.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection10/11/200210/11/200210/11/2002APASS
DetailsTroy Cobbley
fire alarm finaled
DOC - Permit Finaled10/11/200210/11/200210/11/2002APASS
DetailsTroy Cobbley
Finaled by inspector at 10/11/2002 11:13:54 AM
INSP-Final Inspection10/8/200210/10/200210/10/2002AFAIL
DetailsTroy Cobbley
provide an updated one line with the correct zone numbers for the fire inspector and provide the same for a building map 10/10/2002 10:47:12 AM
CHANGE STATUS TO (ISS)  10/8/2002 DONE
resubmittal changed status
Alarm Plan Check9/30/2002 10/4/2002 PASS
Resubmittal made after 1st inspection of installation, to reflect the actual horn strobes installed; new cut sheets and battery calculations included. No other changes to plans.
PLANS/APPL TAKEN TO FRONT DESK  10/4/2002 DONE
A $100 fee applies for this additional review -10/4/2002.
Inspection Record Card- Fire10/4/2002 10/4/2002 DONE
Telephone call  10/4/2002 DONE
resub ready and fees due
Application received  9/30/2002 DONE
resubmittal received for previously issued plans.
INSP-Final Inspection9/23/20029/24/20029/24/2002PFAIL
DetailsTroy Cobbley
strobe overspaced in n.e. corner of building #4, provide weatherproof listing for the A/V installed on the exterior wall, provide revised battery calculations for the a/v's since what is installed is not what was submitted, wire the circuits to match the plans submitted, clean up the wiring in the fire alarm panel, the inspection was stopped due to the problems listed above 9/24/2002 2:31:26 PM
PLANS/APPL TAKEN TO FRONT DESK  7/11/2002 DONE
Inspection Record Card- Fire7/11/2002 7/11/2002 DONE
Telephone call  7/11/2002 DONE
PERMIT READY AND FEES DUE
Issue and Print Permit  7/11/2002 DONE
Plan assigned to (SAM)4/15/2002 7/11/2002 DONE
7/11/2002 15:08:37 SLR - activity updated through activity FIRA22 from case FIR02-00151.
Alarm Plan Check  7/11/2002 PASS
7/11/02 Alan at Alarmco called with necessary information.
Telephone call  7/11/2002 DONE
Alarm at Alarmco called; provided additional information on multiplex design, and ceiling shape in gymnasiums to confirm detector placement. Can now complete plan review.
Alarm Plan Check  7/10/2002 HOLD
Additional information required. Awaiting call from Alarmco to discuss.
Meeting  6/27/2002 DONE
1 hour meeting with Alan Manor, Alarmco to discuss the 6/17/resubmittal which still did not include the information specifically requested in the original review comments. The 2nd set of plans returned to him for revision.
Alarm Plan Check6/17/2002 6/27/2002 FAIL
Resubmittal did not include information specifically required in original reivew comments. No further review done. One set of plans returned to Alarmco for revision.
Miscellaneous action  5/9/2002 DONE
one set of plans returned to Alarmco for revision.
Alarm Plan Check  5/2/2002 FAIL
Review faxed to Alarmco. Plans inadequate for a full review.
Application received  4/15/2002