INSP-Final Inspection | 7/10/2002 | 7/10/2002 | 7/10/2002 | P | PASS |
Troy Cobbley
|
|
|
fire sprinkler system finaled 7/10/2002 3:41:14 PM
|
DOC - Permit Finaled | 7/10/2002 | 7/10/2002 | 7/10/2002 | P | PASS |
Troy Cobbley
|
|
|
Finaled by inspector at 7/10/2002 3:41:21 PM
|
INSP-Final Inspection | 7/9/2002 | 7/9/2002 | 7/9/2002 | P | FAIL |
Troy Cobbley
|
|
|
provide verification that the flame spread rate for the fiberglass backing is less than 25 or add upright protection, pendant sprinkler heads appear to be overspaced above the mezzanine (130 max), provide inspection tag for riser and facp 7/9/2002 4:01:45 PM
|
Inspection Record Card- Fire | 7/8/2002 | | 7/8/2002 | | DONE |
|
|
|
|
Telephone call | | | 7/8/2002 | | DONE |
|
|
|
|
Issue permit | | | 7/8/2002 | | |
|
|
|
|
Plan assigned to (Bill) | 7/1/2002 | | 7/8/2002 | | DONE |
|
|
|
7/8/2002 11:22:14 JWA - activity updated through activity FIRA22 from case FIR02-00264.
|
Sprinkler Plan Check | 7/3/2002 | | 7/8/2002 | | PASS |
Bill Alexander
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 7/8/2002 | | DONE |
Bill Alexander
|
|
|
|
Telephone call | | | 7/2/2002 | | DONE |
|
|
|
plans denied called to have them picked up
|
Application received | | | 7/1/2002 | | |
|
|
|
|
Sprinkler Plan Check | 7/1/2002 | | 7/1/2002 | | FAIL |
Bill Alexander
|
|
|
Plans lack required information/clarification (reference review)
|
Telephone call | | | 7/1/2002 | | DONE |
|
|
|
Faxed copy of review to T.V.
|
Miscellaneous action | | | 7/1/2002 | | DONE |
|
|
|
Took plans to front desk for calling/pickup/return.
|
Case Summary | | | | | DONE |
|
|
|
|