Permit Information
Permit NumberFIR03-00087
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 5550 W MORRIS HILL RD
Project NameSPR CNTY MORGUE OFFICES
Customer Number 
ePlanReview 
Description
(ADA COUNTY CORONER - MORGUE) To install fire sprinkler protection in approximately 1,735 ft/2 area of rest rooms and administrative offices on the 1st floor and 2,385 ft/2 area of rest rooms and administrative offices on the 2nd floor within an existing 24,000 square foot warehouse/office building used by the Ada County Coroner's Office per approved drawings, engineering, and plan review conditions on file. This building is fire sprinklered for area increase. The fire sprinkler system work shall comply with NFPA 13-1999, attached review comment and conditions list, as regulated by the Fire Chief. These notes, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This is work required to meet Fire Department requirements for Fire Code occupancy compliance (Upgrade Agreement letter on file dated 8/22/02). This permit is not attached to a building permit.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Case Summary  7/21/2004 DONE
INSP-Final Inspection6/20/20036/20/20036/20/2003PPASS
DetailsTroy Cobbley
fire sprinklers finaled 6/20/2003 1:43:48 PM
DOC - Permit Finaled6/20/20036/20/20036/20/2003PPASS
DetailsTroy Cobbley
Finaled by inspector at 6/20/2003 1:44:12 PM
Issue and Print Permit  4/28/2003 DONE
Telephone call  4/25/2003 DONE
left mess that permit is ready
Sprinkler Plan Check4/21/2003 4/24/2003 PASS
DetailsBill Alexander
Extensive changes made in the field verification.
PLANS/APPL TAKEN TO FRONT DESK  4/24/2003 DONE
DetailsBill Alexander
Plan resubmittals received  4/21/2003 DONE
INSP-Sprinkler Rough-in/Hydro4/14/20034/16/20034/16/2003APART
DetailsTroy Cobbley
john ###-#### Hydro test for the second and third floors is OK. But items on correction notices still need corrected 4/16/2003 3:32:17 PM
INSP-Sprinkler Rough-in4/16/20034/16/20034/16/2003PFAIL
DetailsTroy Cobbley
Provide fire caulking at the 2" penatration into the warehouse, provide the correct QR pendant in the 2nd floor office and provide the 4 way EQ bracing on the second floor main just before the wall penatration into the warehouse
INSP-Sprinkler Rough-in/Hydro4/16/20034/16/20034/16/2003PFAIL
DetailsTroy Cobbley
Provide city approved resubmitted plans showing all the piping changes. This deficiancy need to be added to the other inspection report for this project for this day
Issue permit  3/12/2003 DONE
Plan assigned to (Bill)3/3/2003 3/11/2003 DONE
3/11/2003 11:54:36 JWA - activity updated through activity FIRA22 from case FIR03-00087.
Sprinkler Plan Check3/3/2003 3/11/2003 PASS
DetailsBill Alexander
PLANS/APPL TAKEN TO FRONT DESK  3/11/2003 DONE
DetailsBill Alexander
Inspection Record Card- Fire3/11/2003 3/11/2003 DONE
Telephone call  3/11/2003 DONE
Application received  3/3/2003