Case Summary | | | 7/21/2004 | | DONE |
|
|
|
|
INSP-Final Inspection | 6/20/2003 | 6/20/2003 | 6/20/2003 | P | PASS |
Troy Cobbley
|
|
|
fire sprinklers finaled 6/20/2003 1:43:48 PM
|
DOC - Permit Finaled | 6/20/2003 | 6/20/2003 | 6/20/2003 | P | PASS |
Troy Cobbley
|
|
|
Finaled by inspector at 6/20/2003 1:44:12 PM
|
Issue and Print Permit | | | 4/28/2003 | | DONE |
|
|
|
|
Telephone call | | | 4/25/2003 | | DONE |
|
|
|
left mess that permit is ready
|
Sprinkler Plan Check | 4/21/2003 | | 4/24/2003 | | PASS |
Bill Alexander
|
|
|
Extensive changes made in the field verification.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 4/24/2003 | | DONE |
Bill Alexander
|
|
|
|
Plan resubmittals received | | | 4/21/2003 | | DONE |
|
|
|
|
INSP-Sprinkler Rough-in/Hydro | 4/14/2003 | 4/16/2003 | 4/16/2003 | A | PART |
Troy Cobbley
|
|
|
john ###-#### Hydro test for the second and third floors is OK. But items on correction notices still need corrected 4/16/2003 3:32:17 PM
|
INSP-Sprinkler Rough-in | 4/16/2003 | 4/16/2003 | 4/16/2003 | P | FAIL |
Troy Cobbley
|
|
|
Provide fire caulking at the 2" penatration into the warehouse, provide the correct QR pendant in the 2nd floor office and provide the 4 way EQ bracing on the second floor main just before the wall penatration into the warehouse
|
INSP-Sprinkler Rough-in/Hydro | 4/16/2003 | 4/16/2003 | 4/16/2003 | P | FAIL |
Troy Cobbley
|
|
|
Provide city approved resubmitted plans showing all the piping changes. This deficiancy need to be added to the other inspection report for this project for this day
|
Issue permit | | | 3/12/2003 | | DONE |
|
|
|
|
Plan assigned to (Bill) | 3/3/2003 | | 3/11/2003 | | DONE |
|
|
|
3/11/2003 11:54:36 JWA - activity updated through activity FIRA22 from case FIR03-00087.
|
Sprinkler Plan Check | 3/3/2003 | | 3/11/2003 | | PASS |
Bill Alexander
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 3/11/2003 | | DONE |
Bill Alexander
|
|
|
|
Inspection Record Card- Fire | 3/11/2003 | | 3/11/2003 | | DONE |
|
|
|
|
Telephone call | | | 3/11/2003 | | DONE |
|
|
|
|
Application received | | | 3/3/2003 | | |
|
|
|
|