INSP-Sprinkler Rough-in | 10/25/2004 | 10/26/2004 | 10/26/2004 | A | PASS |
Rick Jackson
|
|
|
Don, ###-####
|
DOC - Permit Finaled | 10/26/2004 | 10/26/2004 | 10/26/2004 | P | PASS |
Rick Jackson
|
|
|
Finaled by inspector at 10/26/2004 11:35:09 AM
|
Sprinkler Plan Check | 10/13/2004 | | 10/22/2004 | | PASS |
Bill Alexander
|
|
|
Provided calculations for installation fo fire sprinklers exceeding more than 1 head per 1" line outlet. Approved for this design (plans) installation only.
|
Miscellaneous action | | | 10/22/2004 | | DONE |
|
|
|
Approved plans forwarde to permit desk for returning.
|
Case Summary | | | 10/22/2004 | | DONE |
|
|
|
|
Issue and Print Permit | | | 10/22/2004 | | DONE |
|
|
|
|
(F) Reprint permit | | | 10/21/2004 | | DONE |
|
|
|
|
INSP-Sprinkler Rough-in | 10/12/2004 | 10/13/2004 | 10/13/2004 | A | NR |
Rick Jackson
|
|
|
Don, ###-#### Awaititng resubmittals 10/13/2004 3:27:49 PM
|
Plan resubmittals received | | | 10/13/2004 | | DONE |
|
|
|
|
INSP-Sprinkler Rough-in | 10/7/2004 | 10/8/2004 | 10/8/2004 | A | FAIL |
Troy Cobbley
|
|
|
Plans do not match installation. There are multiple pendants off of the same 1" outlet. In one location there were three pendants off of a single outlet. These are pendants that have been modified by the sprinkler contractor. Resubmit plans showing actual piping layout with hydraulic calculations proving existing layout or resubmit plans showing changes required to provide one pendant from one outlet on branchline. 10/8/2004 9:38:45 AM
|
Plan assigned to (Bill) | 9/23/2004 | | 10/4/2004 | | DONE |
|
|
|
|
Sprinkler Plan Check | 9/23/2004 | | 10/4/2004 | | PASS |
Bill Alexander
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 10/4/2004 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 10/4/2004 | | DONE |
|
|
|
|
Telephone call | | | 10/4/2004 | | DONE |
|
|
|
left mess that permit is ready
|
Inspection Record Card- Fire | 10/4/2004 | | 10/4/2004 | | DONE |
|
|
|
|
Issue and Print Permit | | | 10/4/2004 | | DONE |
|
|
|
|
Application received | | | 9/23/2004 | | |
|
|
|
|