Permit Information
Permit NumberFIR04-00587
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 702 W IDAHO ST
Project NameSPR HALL, FARLEY, OBERRECHT &
Customer Number 
ePlanReview 
Description
(HALL, FARLEY, OBERRECHT, AND BLANTON - KEY FINANCIAL - 8TH FLR) To modify and add fire sprinklers for the partial remodel of an existing 6,179-ft/2 office tenant space located on the 8th floor of an existing high-rise building (i.e. the Key Financial building). Fire sprinkler work is associated with interior nonbearing walls, a new 1-hr corridor wall. This building is fire sprinklered because it is a high-rise. The fire sprinkler system work shall comply with IFC 2000, attached review comment and conditions list, as regulated by the Fire Chief. These notes, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to BLD04-01610.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Sprinkler Rough-in10/25/200410/26/200410/26/2004APASS
DetailsRick Jackson
Don, ###-####
DOC - Permit Finaled10/26/200410/26/200410/26/2004PPASS
DetailsRick Jackson
Finaled by inspector at 10/26/2004 11:35:09 AM
Sprinkler Plan Check10/13/2004 10/22/2004 PASS
DetailsBill Alexander
Provided calculations for installation fo fire sprinklers exceeding more than 1 head per 1" line outlet. Approved for this design (plans) installation only.
Miscellaneous action  10/22/2004 DONE
Approved plans forwarde to permit desk for returning.
Case Summary  10/22/2004 DONE
Issue and Print Permit  10/22/2004 DONE
(F) Reprint permit  10/21/2004 DONE
INSP-Sprinkler Rough-in10/12/200410/13/200410/13/2004ANR
DetailsRick Jackson
Don, ###-#### Awaititng resubmittals 10/13/2004 3:27:49 PM
Plan resubmittals received  10/13/2004 DONE
INSP-Sprinkler Rough-in10/7/200410/8/200410/8/2004AFAIL
DetailsTroy Cobbley
Plans do not match installation. There are multiple pendants off of the same 1" outlet. In one location there were three pendants off of a single outlet. These are pendants that have been modified by the sprinkler contractor. Resubmit plans showing actual piping layout with hydraulic calculations proving existing layout or resubmit plans showing changes required to provide one pendant from one outlet on branchline. 10/8/2004 9:38:45 AM
Plan assigned to (Bill)9/23/2004 10/4/2004 DONE
Sprinkler Plan Check9/23/2004 10/4/2004 PASS
DetailsBill Alexander
PLANS/APPL TAKEN TO FRONT DESK  10/4/2004 DONE
Permit Ready to Issue  10/4/2004 DONE
Telephone call  10/4/2004 DONE
left mess that permit is ready
Inspection Record Card- Fire10/4/2004 10/4/2004 DONE
Issue and Print Permit  10/4/2004 DONE
Application received  9/23/2004