Information based on query as of Saturday, September 28, 2024.
Permit Information
Permit NumberFIR04-00654
StatusFinaled
Name ALARMCO
Site Address 10095 W EMERALD ST
Project NamealmEmerald Tech Center-Bldg 10
Customer NumberNOAA
ePlanReview 
Description
To provide a required sprinkler monitoring fire alarm system that includes HVAC shutdown.

FIR04-00682 is associated with building permit BLD 04-00871. These two permits must be completed prior to finalizing FIR04-00654. The building permit is to construct a new 11,504 square foot, one story, concrete tilt-up office and warehouse shell building and related site improvements. This is a shell permit only and no occupancy is allowed under this permit. A separate tenant improvement permit is required to finish this building for occupancy. All construction per the approved plans and attached comment list. This building is fully fire sprinklered. DRH04-00031/PC# 245-04/JCM Emerald Tech Center Building #10 (Shell Only) -

The associated building permit (BLD 04-01918) is to construct a 10,752 square foot office tenant space located within an existing 10,944 square foot building. The building shell was constructed under permit BLD04-00871. Work is to include interior nonbearing walls, 2 restrooms accessible to the disabled, interior doors, suspended ceilings, and finishes all per the approved drawings and the plan review report on file. The fire sprinkler system shall comply with NFPA 13-2002 as regulated by the Fire Department. **CJW** (N.O.A.A. - EMERALD TECH CENTER - BLDG #10) This building is fire sprinklered.

Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection11/17/200411/17/200411/17/2004APASS
DetailsTroy Cobbley
Fire alarm finaled
DOC - Permit Finaled11/17/200411/17/200411/17/2004APASS
DetailsTroy Cobbley
Finaled by inspector at 11/17/2004 9:16:13 AM
INSP-Final Inspection11/15/200411/15/200411/15/2004PFAIL
DetailsTroy Cobbley
Wrong fire alarm panel installed. Install correct panel or resubmit new panel information for approval.
Issue and Print Permit  11/2/2004 DONE
Permit Ready to Issue  10/28/2004 DONE
Inspection Record Card- Fire10/28/2004 10/28/2004 DONE
Telephone call  10/28/2004 DONE
called and talked to wayne inregards to alan that the permit and fee are ready
Plan assigned to (Mary)10/19/2004 10/27/2004 DONE
Alarm Plan Check  10/27/2004 PASS
Approved pending field inspection of fire alarm permit comments.
PLANS/APPL TAKEN TO FRONT DESK  10/27/2004 DONE
Application received  10/19/2004