INSP-Final Inspection | 4/18/2005 | 4/18/2005 | 4/18/2005 | P | PASS |
Troy Cobbley
|
|
|
Fire alarm finaled
|
INSP-Alarm Testing | 4/7/2005 | 4/8/2005 | 4/8/2005 | A | PASS |
Forrest France
|
|
|
Fire alarm finaled
|
Telephone call | | | 3/29/2005 | | DONE |
|
|
|
Bob McKinney (Ada County) ###-####, they need to remove one H/S (correction notice from Troy see activities) as it is mounted too high. They want to increase the candela rating for a single H/S. Doesn't afford appropriate coverage, but the solution that will work is to increase two H/S to 110 cd. (the 30cd on the column and the 75 on the east wall of the reception/lobby space). I have marked up the issued plans and will notify Troy Cobbley (BC) and Rick Groom (Northwest Sales) of the agreement. Revised (as-built) plans will be required from Northwest Sales to the owner. (NFPA 72). Any resubmittals required for the city will be designated by the inspector.
|
INSP-Alarm Testing | 3/21/2005 | 3/22/2005 | 3/22/2005 | A | FAIL |
Troy Cobbley
|
|
|
A/v is mounted too high, repair vav box and provide review comments for inspection 3/22/2005 12:56:31 PM
|
Issue and Print Permit | | | 12/22/2004 | | DONE |
|
|
|
|
Alarm Plan Check | | | 12/21/2004 | | PASS |
|
|
|
Approved pending field inspection of fire alarm permit comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 12/21/2004 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 12/21/2004 | | 12/21/2004 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 12/21/2004 | | |
|
|
|
|
Telephone call | | | 12/21/2004 | | DONE |
|
|
|
lft vm with Rick Groom ###-#### that his permit and fees are ready to be picked up
|
Plan assigned to (Mary) | 11/4/2004 | | 12/21/2004 | | DONE |
|
|
|
|
Plan resubmittals received | | | 12/20/2004 | | DONE |
|
|
|
Received faxed letter from Don Carson (Ada County) that specifies the emergency generator information.
|
Plan resubmittals received | | | 12/20/2004 | | DONE |
|
|
|
Received letter from Don Carson (Ada County) specifying the emergency generator and fuel arrangement. The letter stated they do not have a fuel agreement, but they can get diesel internally to accommodate the code requirement. I called and stated that he would need to specify that the diesel could be delivered within 2 hours. He said he would revise and resend.
|
Telephone call | | | 12/17/2004 | | DONE |
|
|
|
Received a phone call from Bob Mc Kinney, requesting the NFPA code sections for the emergency generator.
|
Miscellaneous action | | | 12/17/2004 | | DONE |
|
|
|
Sent an e-mail with the appropriate NFPA 72/110 code sections.
|
Telephone call | | | 12/8/2004 | | DONE |
|
|
|
Spoke with Ken Summers (Ada County) regarding the type of information I am requesting for the emergency generator. He stated he would have John Logan (safety) contact me.
|
Plan resubmittals received | | | 11/17/2004 | | DONE |
|
|
|
Received a letter that was not specific enough.
|
Telephone call | | | 11/17/2004 | | DONE |
|
|
|
Phoned Don and stated that specifically the generator must meet NFPA 72 4.4.1.9.3.1 and 4.4.1.9.6.3 (B).
|
Telephone call | | | 11/16/2004 | | DONE |
|
|
|
Don Carson, Ada County phoned to find out the emergency generator information that I was requesting from Rick Groom. I explained that the generator needed to comply with NFPA 72 and 110. I would require a letter to define the generator and a copy of a fuel agreement if required.
|
Telephone call | | | 11/10/2004 | | DONE |
|
|
|
Phoned Rick Groom to request the velocity ratings from the manufacturer's information regarding the in-ducr smoke detector and request emergency generator information and a copy of the fuel agreement if required.
|
Plan resubmittals received | | | 11/10/2004 | | DONE |
|
|
|
Received in-duct manufacturer's information via fax.
|
Application received | | | 11/4/2004 | | |
|
|
|
|