Permit Information
Permit NumberFIR04-00698
StatusFinaled
Name NORTHWEST SALES COMPANY
Site Address 200 W FRONT ST
Project Namealm - COURTHOUSE
Customer Number 
ePlanReview 
Description
To replace an existing fire alarm system. The required manual fire alarm system includes HVAC shutdown, fire/smoke damper control, door release and notification throughout.

The associated building permit (BLD 04-02016) is to remodel an existing 10,660 square foot office tenant space located on the 2nd floor of the Ada County Courthouse. Selective nonstructural demolition work is also covered under this permit. Work is to include nonbearing walls, glass block walls, doors, windows, millwork, suspended ceilings, and finishes all per the approved drawings and the plan review report on file. Within the remodel area, the location of fire sprinkler heads shall comply with NFPA 13-2002 as regulated by the Fire Department. **CJW** (ADA COUNTY DEVELOPMENT SERVICES DEPARTMENT - 2ND FLOOR) This building is fire sprinkered because it has an occupied floor more than 55 feet above the ground.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection4/18/20054/18/20054/18/2005PPASS
DetailsTroy Cobbley
Fire alarm finaled
INSP-Alarm Testing4/7/20054/8/20054/8/2005APASS
DetailsForrest France
Fire alarm finaled
Telephone call  3/29/2005 DONE
Bob McKinney (Ada County) ###-####, they need to remove one H/S (correction notice from Troy see activities) as it is mounted too high. They want to increase the candela rating for a single H/S. Doesn't afford appropriate coverage, but the solution that will work is to increase two H/S to 110 cd. (the 30cd on the column and the 75 on the east wall of the reception/lobby space). I have marked up the issued plans and will notify Troy Cobbley (BC) and Rick Groom (Northwest Sales) of the agreement. Revised (as-built) plans will be required from Northwest Sales to the owner. (NFPA 72). Any resubmittals required for the city will be designated by the inspector.
INSP-Alarm Testing3/21/20053/22/20053/22/2005AFAIL
DetailsTroy Cobbley
A/v is mounted too high, repair vav box and provide review comments for inspection 3/22/2005 12:56:31 PM
Issue and Print Permit  12/22/2004 DONE
Alarm Plan Check  12/21/2004 PASS
Approved pending field inspection of fire alarm permit comments.
PLANS/APPL TAKEN TO FRONT DESK  12/21/2004 DONE
Inspection Record Card- Fire12/21/2004 12/21/2004 DONE
Permit Ready to Issue  12/21/2004  
Telephone call  12/21/2004 DONE
lft vm with Rick Groom ###-#### that his permit and fees are ready to be picked up
Plan assigned to (Mary)11/4/2004 12/21/2004 DONE
Plan resubmittals received  12/20/2004 DONE
Received faxed letter from Don Carson (Ada County) that specifies the emergency generator information.
Plan resubmittals received  12/20/2004 DONE
Received letter from Don Carson (Ada County) specifying the emergency generator and fuel arrangement. The letter stated they do not have a fuel agreement, but they can get diesel internally to accommodate the code requirement. I called and stated that he would need to specify that the diesel could be delivered within 2 hours. He said he would revise and resend.
Telephone call  12/17/2004 DONE
Received a phone call from Bob Mc Kinney, requesting the NFPA code sections for the emergency generator.
Miscellaneous action  12/17/2004 DONE
Sent an e-mail with the appropriate NFPA 72/110 code sections.
Telephone call  12/8/2004 DONE
Spoke with Ken Summers (Ada County) regarding the type of information I am requesting for the emergency generator. He stated he would have John Logan (safety) contact me.
Plan resubmittals received  11/17/2004 DONE
Received a letter that was not specific enough.
Telephone call  11/17/2004 DONE
Phoned Don and stated that specifically the generator must meet NFPA 72 4.4.1.9.3.1 and 4.4.1.9.6.3 (B).
Telephone call  11/16/2004 DONE
Don Carson, Ada County phoned to find out the emergency generator information that I was requesting from Rick Groom. I explained that the generator needed to comply with NFPA 72 and 110. I would require a letter to define the generator and a copy of a fuel agreement if required.
Telephone call  11/10/2004 DONE
Phoned Rick Groom to request the velocity ratings from the manufacturer's information regarding the in-ducr smoke detector and request emergency generator information and a copy of the fuel agreement if required.
Plan resubmittals received  11/10/2004 DONE
Received in-duct manufacturer's information via fax.
Application received  11/4/2004