Permit Information
Permit NumberFIR05-00061
StatusVoid/No Violation
Name AUDIO ELECTRONICS INC
Site Address 802 W BANNOCK ST
Project NameHOFF BUILDING-12/13/MEZZ
Customer Number 
ePlanReview 
Description
To provide required total area smoke detection and notification (speaker/strobes) on the core areas of the 12th, 14th and penthouse floors (NO OCCUPANCY). The required manual fire alarm system includes required automatic detection, HVAC shutdown, fire/smoke damper control, door release and notification (speaker/strobes) throughout. As this is a high rise, the fire department communication system is required in all elevators, elevator lobbies and inside enclosed stairwells at each floor.

The associated building permit (BLD 04-02671) is to perform shell work within the Hoff Building (basement, 12th story, 13th story, and the 13th story mezzanine). Work is to include upgrading the basement and 12th story restrooms to be accessible to the disabled. The interior walls and doors of the existing "open exterior stairway" will also be reconfigured on the 12th story. A 2-hr wall will be constructed and a 90 minute door will be installed. This permit does NOT establish a Certificate of Occupancy for any tenant. Shell work on the 12th story, 13th story, and the 13th story mezzanine was done in anticipation of a future office tenant who will occupy all 3 levels. All work shall comply with the approved drawings, the plan review report, and all applicable codes. The location of fire sprinkler heads shall comply with NFPA 13-2002 as regulated by the Fire Department. **CJW** (HOFF BUILDING - BASEMENT, 12 STORY, 13TH STORY, AND 13TH STORY MEZZANINE)

To provide required total area smoke detection and notification (speaker/strobes) on the core areas of the 12th, 14th and penthouse floors (NO OCCUPANCY). The required manual fire alarm system includes required automatic detection, HVAC shutdown, fire/smoke damper control, door release and notification (speaker/strobes) throughout. As this is a high rise, the fire department communication system is required in all elevators, elevator lobbies and inside enclosed stairwells at each floor.

The associated building permit (BLD 04-02671) is to perform shell work within the Hoff Building (basement, 12th story, 13th story, and the 13th story mezzanine). Work is to include upgrading the basement and 12th story restrooms to be accessible to the disabled. The interior walls and doors of the existing "open exterior stairway" will also be reconfigured on the 12th story. A 2-hr wall will be constructed and a 90 minute door will be installed. This permit does NOT establish a Certificate of Occupancy for any tenant. Shell work on the 12th story, 13th story, and the 13th story mezzanine was done in anticipation of a future office tenant who will occupy all 3 levels. All work shall comply with the approved drawings, the plan review report, and all applicable codes. The location of fire sprinkler heads shall comply with NFPA 13-2002 as regulated by the Fire Department. **CJW** (HOFF BUILDING - BASEMENT, 12 STORY, 13TH STORY, AND 13TH STORY MEZZANINE)

Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Permit VOIDED2/26/20092/26/20092/26/2009 DONE
DetailsRita DeYoung
per Jason Minnick not finishing job.
INSP-Final Inspection6/1/20056/1/20056/1/2005PPART
DetailsForrest France
Fire alarm passed inspection on the 12th floor only.
Issue and Print Permit  6/1/2005 DONE
Alarm Plan Check  5/26/2005 PASS
Plan Modification. Approved pending field inspection of fire alarm permit comments.
PLANS/APPL TAKEN TO FRONT DESK  5/26/2005 DONE
Inspection Record Card- Fire5/26/2005 5/26/2005 DONE
Telephone call  5/26/2005 DONE
called spoke to cynthia permit is ready and fees
Plan resubmittals received  5/24/2005  
INSP-Final Inspection5/5/20055/6/20055/6/2005PFAIL
DetailsForrest France
Fail inspection, provide correct cd rating on strobes in reception area as per. plan indicates. Provide smoke alarm address correction to match floor plan of restrooms (men's and women's). Provide pull station that matches type on submittals at address
Issue permit  4/13/2005 DONE
Alarm Plan Check  4/12/2005 PASS
Approved pending field inspection of fire alarm permit comments.
PLANS/APPL TAKEN TO FRONT DESK  4/12/2005 DONE
Inspection Record Card- Fire4/12/2005 4/12/2005 DONE
Permit Ready to Issue  4/12/2005 DONE
Telephone call  4/12/2005 DONE
left mess that permit is ready
Plan assigned to (Mary)1/31/2005 4/12/2005 DONE
Plan resubmittals received  4/7/2005  
Alarm Plan Check  4/4/2005 PART
Partial approval for 12th floor only. Resubmittal is required for the 14th floor.
PLANS/APPL TAKEN TO FRONT DESK  4/4/2005 DONE
Inspection Record Card- Fire4/4/2005 4/4/2005 DONE
Permit Ready to Issue  4/4/2005 DONE
Issue and Print Permit  4/4/2005 DONE
Plan resubmittals received  3/29/2005 DONE
Miscellaneous action  2/10/2005 DONE
Plans on HOLD. FA permit scope of work does not match up with the BLDG permit scope of work. I spoke with Jason Minnick at AEI, he'll check into the project and get back to me.
Application received  1/31/2005