Permit Information
Permit NumberFIR05-00437
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 12585 W EXPLORER DR
Project NameSPR CONECTL
Customer Number 
ePlanReview 
Description
(CONECTL) To add and relocated existing fire sprinklers for the remodel of an existing 11,412-ft/2 building for a commercial tenant. Fire sprinkler work is related to new interior partitions, installation of new suspended ceiling system with new lighting and HVAC system. Occupancies include 7,732-ft/2 of office, 1,980-ft/2 of storage, and 1,700-ft/2 of fabrication areas for machine shop and engineering labs. Any Racking will require a separate application and permit. This building is fully fire sprinklered. This fire protection work shall comply with the IFC 2003 and the permit review comments; each regulated by the Fire Chief. The review comments, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to BLD05-01529.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/31/20059/1/20059/1/2005APASS
DetailsForrest France
Fire sprinkler permit finaled.
INSP-Conference8/30/20058/31/20058/31/2005ADONE
DetailsForrest France
Duplicate inspection, already completed.
INSP-Sprinkler Rough-in8/30/20058/31/20058/31/2005AFAIL
DetailsForrest France
Quick and standard response heads are mixed within the same room, three heads piped off 1" in 3 areas as marked on plans is not allowed unless the required fire separation rating can be met, provide head guards on SW heads below overhead doors.
Sprinkler Plan Check8/16/2005 8/30/2005 PASS
DetailsBill Alexander
8/30/2005-Don Weland, provided revised 8.5 x 11 plan sheet and explanation letter.
08/29/2005-Per Trent Bice-Reference telephone activity conversation (same date).
Plan assigned to (Bill)8/16/2005 8/30/2005 DONE
DetailsBill Alexander
PLANS/APPL TAKEN TO FRONT DESK  8/30/2005 DONE
Inspection Record Card- Fire8/30/2005 8/30/2005 DONE
Permit Ready to Issue  8/30/2005 DONE
Telephone call  8/30/2005 DONE
tlk to lilly that their permit and fees are ready to be picked up
Issue permit  8/30/2005 DONE
Telephone call  8/29/2005 DONE
Contacted Trent Bice-regarding problems with resubmittal information provided.
1. Six heads on 1 1/2" in the warehouse and original indicates a design for five?
2. Corridor and Golf Lab (room 116) problems. Relocating heads corridor will overspace heads in the Golf Lab.
3. Habitec letter indicates racks will be used in the warehouse. Desinger needs to supply clarification of racks for IFC fire protection (possible) requirements addressing the same.

Trent indicated he wanted to put the review on hold.
Plan resubmittals received  8/16/2005 DONE
Issue and Print Permit  8/2/2005 DONE
Plan assigned to (Bill)7/20/2005 8/1/2005 DONE
PLANS/APPL TAKEN TO FRONT DESK  8/1/2005 DONE
Sprinkler Plan Check7/20/2005 8/1/2005 PART
DetailsBill Alexander
Inspection Record Card- Fire8/1/2005 8/1/2005 DONE
Inspection Record Card- Fire8/1/2005 8/1/2005 DONE
Permit Ready to Issue  8/1/2005 DONE
Telephone call  8/1/2005 DONE
lft ms for trent bide ###-#### that permit and fees are ready to be picked up
Telephone call  8/1/2005 DONE
tlk to john warnick ###-#### that permit and fees are ready to be picked up
Case Summary  7/20/2005 DONE
Application received  7/20/2005