INSP-Final Inspection | 8/31/2005 | 9/1/2005 | 9/1/2005 | A | PASS |
Forrest France
|
|
|
Fire sprinkler permit finaled.
|
INSP-Conference | 8/30/2005 | 8/31/2005 | 8/31/2005 | A | DONE |
Forrest France
|
|
|
Duplicate inspection, already completed.
|
INSP-Sprinkler Rough-in | 8/30/2005 | 8/31/2005 | 8/31/2005 | A | FAIL |
Forrest France
|
|
|
Quick and standard response heads are mixed within the same room, three heads piped off 1" in 3 areas as marked on plans is not allowed unless the required fire separation rating can be met, provide head guards on SW heads below overhead doors.
|
Sprinkler Plan Check | 8/16/2005 | | 8/30/2005 | | PASS |
Bill Alexander
|
|
|
8/30/2005-Don Weland, provided revised 8.5 x 11 plan sheet and explanation letter.
08/29/2005-Per Trent Bice-Reference telephone activity conversation (same date).
|
Plan assigned to (Bill) | 8/16/2005 | | 8/30/2005 | | DONE |
Bill Alexander
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 8/30/2005 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 8/30/2005 | | 8/30/2005 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 8/30/2005 | | DONE |
|
|
|
|
Telephone call | | | 8/30/2005 | | DONE |
|
|
|
tlk to lilly that their permit and fees are ready to be picked up
|
Issue permit | | | 8/30/2005 | | DONE |
|
|
|
|
Telephone call | | | 8/29/2005 | | DONE |
|
|
|
Contacted Trent Bice-regarding problems with resubmittal information provided.
1. Six heads on 1 1/2" in the warehouse and original indicates a design for five?
2. Corridor and Golf Lab (room 116) problems. Relocating heads corridor will overspace heads in the Golf Lab.
3. Habitec letter indicates racks will be used in the warehouse. Desinger needs to supply clarification of racks for IFC fire protection (possible) requirements addressing the same.
Trent indicated he wanted to put the review on hold.
|
Plan resubmittals received | | | 8/16/2005 | | DONE |
|
|
|
|
Issue and Print Permit | | | 8/2/2005 | | DONE |
|
|
|
|
Plan assigned to (Bill) | 7/20/2005 | | 8/1/2005 | | DONE |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 8/1/2005 | | DONE |
|
|
|
|
Sprinkler Plan Check | 7/20/2005 | | 8/1/2005 | | PART |
Bill Alexander
|
|
|
|
Inspection Record Card- Fire | 8/1/2005 | | 8/1/2005 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 8/1/2005 | | 8/1/2005 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 8/1/2005 | | DONE |
|
|
|
|
Telephone call | | | 8/1/2005 | | DONE |
|
|
|
lft ms for trent bide ###-#### that permit and fees are ready to be picked up
|
Telephone call | | | 8/1/2005 | | DONE |
|
|
|
tlk to john warnick ###-#### that permit and fees are ready to be picked up
|
Case Summary | | | 7/20/2005 | | DONE |
|
|
|
|
Application received | | | 7/20/2005 | | |
|
|
|
|