INSP-Final Inspection | 2/26/2007 | 2/27/2007 | 2/27/2007 | A | PASS |
Forrest France
|
|
|
Per inspection completed 12/5/05, FA final inspection passed. Permit finaled.
|
(F) Reprint permit | | | 2/16/2007 | | |
|
|
|
|
INSP-Alarm Testing | 12/5/2005 | 12/5/2005 | 12/5/2005 | P | PASS |
Forrest France
|
|
|
c/n items have been performed, fire alarm passed inspection.
|
Miscellaneous action | | | 11/2/2005 | | DONE |
|
|
|
Confirmed the FACP was installed in 1997, therefore will assume the 1994UFC was implemented. The audibility requirement for the hotel rooms from the FA system is not required per the exception of 1007.3.3.3.1.
|
INSP-Final Inspection | 10/25/2005 | 10/26/2005 | 10/26/2005 | A | FAIL |
Troy Cobbley
|
|
|
The resident rooms do not meet the minimum sound requirements and the a/vs in the entry ways exceed 15' from the walls. Entry ways may be considered rooms if Mary agrees but strobe candella is still lacking. Interconnection between new NAC and panel has been tested and passed. End of line voltage for both NAC circuits has been tested and passed. Sound levels in the common areas passed.
|
Plan assigned to (Mary) | 9/28/2005 | | 10/10/2005 | | DONE |
|
|
|
|
Alarm Plan Check | | | 10/10/2005 | | PASS |
|
|
|
Approved pending field inspection of fire alarm permit comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 10/10/2005 | | DONE |
|
|
|
|
Telephone call | | | 10/10/2005 | | DONE |
|
|
|
Left message for Rob that permit is ready & fees///10/10/05 11:05am BAS
|
Permit Ready to Issue | | | 10/10/2005 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 10/10/2005 | | 10/10/2005 | | DONE |
|
|
|
|
Issue permit | | | 10/10/2005 | | |
|
|
|
|
Case Summary | | | 9/28/2005 | | DONE |
|
|
|
|
Application received | | | 9/28/2005 | | |
|
|
|
|