INSP-Final Inspection | 10/13/2006 | 10/13/2006 | 10/13/2006 | P | PASS |
Forrest France
|
|
|
Fire alarm permit finaled.
|
INSP-Alarm Testing | 10/11/2006 | 10/12/2006 | 10/12/2006 | A | PASS |
Forrest France
|
|
|
Corrections have been verified for completion, inspection passed.
|
INSP-Alarm Testing | 10/10/2006 | 10/11/2006 | 10/11/2006 | P | CANC |
Troy Cobbley
|
|
|
No time for inspection due to time constraints and micron plan review
|
INSP-Alarm Testing | 10/9/2006 | 10/10/2006 | 10/10/2006 | P | FAIL |
Troy Cobbley
|
|
|
See as-built drawings for corrections needed on the first and second floors. The monitoring agency did not receive any alarm signals. All items will need to be retested. Third floor items have been corrected.
|
INSP-Alarm Testing | 10/6/2006 | 10/9/2006 | 10/9/2006 | A | PART |
Forrest France
|
|
|
Items tested today include complete sprinkler monitoring and notification and detection devices for the third floor only. Noted the first floor zone tamper and the standpipe control tamper are addressed as the same point, two duct detectors on the 3rd floor as noted on approved plans are poorly located and will require changed configuration or a magnehelic test, damper for ID 173 as marked on plans operates backwards, covers on some strobes were removed while on site. As builts for field mods have been provided. Inspection concluded after two hours on site due to time constraints, still need to test 1st and 2nd floors, verify signals, verifiy corrections for the 3rd floor as noted today.
|
INSP-Alarm Testing | 10/4/2006 | 10/6/2006 | 10/6/2006 | P | CANC |
Troy Cobbley
|
|
|
No time left in day for inspection
|
INSP-Alarm Testing | 10/4/2006 | 10/5/2006 | 10/4/2006 | P | CANC |
Troy Cobbley
|
|
|
Forrest or Troy, Will 4:00PM work on Thursday? Please Let me Know. Thanks Mike; Phone #: ###-#### Internet Inspection Request from: Mike Timmerman Inspection cancelled from web by: Mike Timmerman
|
Issue and Print Permit | | | 3/14/2006 | | DONE |
|
|
|
|
Alarm Plan Check | | | 3/10/2006 | | PASS |
|
|
|
Approved pending field inspection of fire alarm permit comments.
|
Plan assigned to (Mary) | 1/26/2006 | | 3/10/2006 | | DONE |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 3/10/2006 | | DONE |
|
|
|
|
Telephone call | | | 3/10/2006 | | DONE |
|
|
|
called ###-#### and left message w/Melissa for Mike that permit is ready and no fee
|
Inspection Record Card- Fire | 3/10/2006 | | 3/10/2006 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 3/10/2006 | | DONE |
|
|
|
|
Plan resubmittals received | | | 3/3/2006 | | DONE |
|
|
|
|
Alarm Plan Check | | | 2/7/2006 | | FAIL |
|
|
|
Resubmittal required. Faxed comments to Mike Timmerman (M2) and Craig Hasselstrom (Eidam)
|
Application received | | | 1/26/2006 | | |
|
|
|
|
Case Summary | | | 1/26/2006 | | |
|
|
|
|