Information based on query as of Friday, September 27, 2024.
Permit Information
Permit NumberFIR06-00562
StatusFinaled
Name M2 AUTOMATION
Site Address 150 N CAPITOL BLVD
Project NameCITY HALL
Customer Number 
ePlanReview 
Description
To add required devices to both elevators to bring shunt trip/recall and Firemans's hat annunciation up to current code.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection10/24/200710/25/200710/25/2007APASS
DetailsForrest France
Final inspection passed per K. Roule, fire alarm permit finaled.
INSP-Final Inspection10/21/200710/23/200710/23/2007APART
DetailsForrest France
Building one elevator testing passed, final pending building two elevator recall functional test, all other items are acceptable.
INSP-Final Inspection10/12/200710/16/200710/16/2007APART
DetailsForrest France
One HD at building one elevator equip penthouse is not functional, shunt trip and voltage monitoring at bldg. 2 elevator tested okay. Need to test recall at both elevators, retest one HD, and review approved plans at next inspection.
FIR-Aging Inspection3/2/20073/2/20073/5/2007 DONE
DetailsForrest France
wip
Issue and Print Permit  8/22/2006 DONE
Alarm Plan Check  8/16/2006 PASS
Approved without written review comments
PLANS/APPL TAKEN TO FRONT DESK  8/16/2006 DONE
Inspection Record Card- Fire8/16/2006 8/16/2006 DONE
Permit Ready to Issue  8/16/2006 DONE
Telephone call  8/16/2006 DONE
tlk to mw automation that permit and fees are ready to be picked up
Case Summary  8/1/2006 DONE
Application received  8/1/2006  
Plan assigned to (Mary)8/1/2006