Information based on query as of Friday, September 27, 2024.
Permit Information
Permit NumberFIR07-00243
StatusFinaled
Name DELTA FIRE SYSTEMS
Site Address 1455 S CAPITOL BLVD
Project NameMarriott Towne Place Suites
Customer Number 
ePlanReview 
Description
Add fire sprinklers through-out this new 72,923 ft/2 four story 123 unit hotel. The fire sprinklers are being added for area increase. The system will include a wet pipe system serving through-out the heated areas, and a dry pipe system to serve the attic space.
The fire sprinkler system work shall comply with the IFC 2003, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to building permit: BLD06-00456. This permit is also attached to the under ground fire service work permit: FIR06-00727Revised Scope of Work As-Built Dated 01/08/2008:
Add fire sprinklers in the attic space beneath the over builds. This work does not appear to adversely affect the remote area of operation in the attic. The modifications in the attic are noted as Rev. D and dated 01/08/08. Other revisions where minor, such as relocating two heads in the fourth floor corridor. A total of 26 heads were affected as a result of the modifications.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection2/8/20082/11/20082/11/2008APASS
DetailsForrest France
Fire sprinkler system final testing passed, previous correction items are complete, plan resubmittals provided, three defficiencies noted at today's inspection repaired while on site, dry system trip test and DCVA forward flow testing passed. See project related permit FIR06-00727 for the balance of activities and inspections completed for this overhead work listed under the UG permit due to contractor mixing permit #'s for site inspeciton requests.
Plan assigned to (SAM)1/28/2008 2/8/2008 PASS
DetailsCathy Brown
2/8/2008 14:34:58 CMB - activity updated through activity FIRA22 from case FIR07-00243.
Telephone call  2/8/2008 DONE
Telcon from Clarence, regarding status. I confirmed they are still in process, the 10-day normal turnaround for plan modifications will be Monday. Called Brian J, left voice message to call Clarence directly with status. I confirmed he can schedule inspection same day permit is re-issued; can get inspection same day if received before noon; or next morning if received afternoon. I also spoke with Forrest; he's overbooked today but will give this inspection priority as soon as it gets scheduled.
PLANS/APPL TAKEN TO FRONT DESK  2/8/2008  
Inspection Record Card- Fire2/8/2008 2/8/2008 DONE
DetailsCathy Brown
Permit Ready to Issue  2/8/2008 DONE
Issue and Print Permit  2/8/2008  
Sprinkler Plan Check1/28/2008 2/7/2008 PASS
Details
This review was the 4th, of this review 26 additional heads were affected. *As-Built Plans are Approved by Bryan Johnson
INSP-Final Inspection1/24/20081/28/20081/28/2008PFAIL
DetailsForrest France
Need plan resubmittals per field inspection notes completed 6/27/07 for the dry system modifications, the paddle style waterflow switch at the dry system riser is not allowed, provide a QR head at the first floor SE storage room, need to provide a seal or lock at the ball valve to the pressure switch at the dry system trim, noted mixed response heads at three rooms on the second floor including 212 and 223, one head at room 236 is obstructed by a light fixture, noted items from the previous inspection at the 1st floor are complete, inspection concluded at this time due to time constraints.
Plan resubmittals received  1/28/2008  
Plan Modification: Received three copies of as-built drawings and application
INSP-Sprinkler Rough-in1/14/20081/18/20081/18/2008APART
DetailsForrest France
First floor corridor fire sprinklers are okay for cover with the exception of two pendents in need of relocation due to overspacing from adjacent vestibules to the meeting room, also noted one head blocked by a 4' soffit at the lobby, missing head at the laundry chute termination room, discussed head location at a mech. room, the elevator pit head is not yet installed, missing escutcheons at some locations.
Telephone call  1/14/2008 DONE
Received package from Delta Fire for project FIR07-00243, the plans are marked As-Built. Called Forrest to find out if he asked for the As-Built plans to be submitted to Boise City and if these plans are resubmittal review plans or just as-built, Forrest was not aware of what these plans were for. Called Delta Fire Office talked to Ron Holmgren asked Ron if these plans were for resubmittal or As-Built, Ron said they were As-Built. I told him I would take the plans to the front desk for Delta to pickup and have ready for field inspection.
INSP-Sprinkler Rough-in/Hydro8/9/20078/10/20078/10/2007APART
DetailsForrest France
Heads at the laundry chute are okay for cover, noted one hanger at the 2nd floor piping to the chute in need of attatchment.
Issue and Print Permit  6/5/2007 DONE
Inspection Record Card- Fire6/4/2007 6/4/2007 DONE
PLANS/APPL TAKEN TO FRONT DESK  6/4/2007 DONE
Telephone call  6/4/2007 DONE
tlk to michael mead ###-#### that permit and no fee ready to be picked up
Permit Ready to Issue  6/4/2007 DONE
Sprinkler Plan Check5/16/2007 5/31/2007 PASS
Plans are approved by Bryan Johnson
Issue and Print Permit  4/4/2007 DONE
Inspection Record Card- Fire4/3/2007 4/3/2007 DONE
Sprinkler Plan Check3/16/2007 4/3/2007 PASS
Plans are approved with Conditions for Wet Pipe by Bryan Johnson
Telephone call  4/3/2007  
lft vm with michael mead ###-#### that permit is ready to be picked up
Permit Ready to Issue  4/3/2007 DONE
Application received  3/16/2007  
Pending Assignment by SAM3/16/2007