Information based on query as of Friday, September 27, 2024.
Permit Information
Permit NumberFIR07-00643
StatusFinaled
Name VIKING AUTOMATIC SPRINKLER CO
Site Address 6840 S EISENMAN RD
Project NameCORNINGWARE
Customer Number 
ePlanReview 
Description
overheadThe Permitted Work Scope: Over Head Only
Modify the existing system by adding and relocating heads to accommodate a new wall and ceiling layout in suites 6840 & 6830. This review is limited to the interior of the project.
The fire sprinkler system work shall comply with the IFC 2003, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to BLD07-01644. When tenant work affects fire sprinkler protection outside the permitted work area due to the installation of tenant-demising or new partition walls, the affected area sprinkler coverage outside the BLD permit will fall under the Fire Permit scope of work, to maintain the required fire protection within the fire sprinklered facility. The “Riser” and its supplies which include all appurtenances (including tamper, alarm and alarm monitoring) relating to the normal and correct function and integrity of this system will fall under the jurisdiction for code compliant verification.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/27/20078/28/20078/27/2007PPASS
DetailsForrest France
Final fire sprinkler inspection passed, permit finaled.
INSP-Final Inspection8/16/20078/17/20078/17/2007PPART
DetailsForrest France
Necessary corrections have been made, OH install is approved for cover at the drop ceilings, final pending ceiling tile and escutcheons.
INSP-Sprinkler Rough-in/Hydro8/15/20078/16/20078/16/2007AFAIL
DetailsForrest France
Heads at several locations including along the west wall of the sales floor exceed maximum allowed spacing for OH group 2 as designed. The hydrostatic test passed.
Issue and Print Permit  8/15/2007 DONE
PLANS/APPL TAKEN TO FRONT DESK  8/14/2007 DONE
Inspection Record Card- Fire8/14/2007 8/14/2007 DONE
Telephone call  8/14/2007  
tlk to rick reynolds ###-#### that permit and fees are ready to be picked up
Permit Ready to Issue  8/14/2007 DONE
Sprinkler Plan Check7/25/2007 8/13/2007 PASS
Plans are approved as submitted by Bryan Johnson
Telephone call  8/10/2007 DONE
telcon from Carrie, CSDI re status of reviw. Should be done by Monday. Suggested she ask contractor to send in an Early Start Request, which would allow them to start immediately.
Miscellaneous action  8/10/2007 DONE
Approved Early Start request to begin installation work per submitted plans. Copy attached.
Application received  7/25/2007  
Case Summary  7/25/2007 DONE
Pending Assignment by SAM7/25/2007