Miscellaneous action | | | 7/19/2010 | | DONE |
|
|
|
Taken to records for scanning.
|
INSP-Final Inspection | 6/2/2010 | 6/3/2010 | 6/3/2010 | A | PASS |
Forrest France
|
|
|
Inspection passed, fire sprinkler permit final approved.
|
INSP-Final Inspection | 4/16/2010 | 4/16/2010 | 4/16/2010 | P | PART |
Forrest France
|
|
|
Noted foil at one upright head below the new stairs to be removed, provide verification of a current annual inspection for the exisitng sprinkler system. Remainder of new installation is satisfactory.
|
INSP-Sprinkler Rough-in | 2/16/2010 | 2/16/2010 | 2/18/2010 | P | PART |
Forrest France
|
|
|
Contact Phone #: ###-####
|
INSP-Sprinkler Rough-in/Hydro | 2/4/2010 | 2/5/2010 | 2/9/2010 | A | PART |
Forrest France
|
|
|
Overhead work appears satisfactory, however missing approved/stamped plans on site for verification. Documents provided include data sheets, permit application, calcs.
|
Plan assigned to (Tim) | 1/8/2010 | | 1/11/2010 | | DONE |
Tim Frost
|
|
|
1/11/2010 09:44:10 TRF - activity updated through activity FIRA22 from case FIR10-00004.
|
Sprinkler Plan Check | 1/11/2010 | | 1/11/2010 | | PASS |
Tim Frost
|
|
|
Please, see attached comments.
There are annotations on the plans.
|
1st review completed | | | 1/11/2010 | | DONE |
Tim Frost
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 1/11/2010 | | DONE |
Tim Frost
|
|
|
|
Inspection Record Card- Fire | 1/11/2010 | | 1/11/2010 | | DONE |
|
|
|
|
Telephone call | | | 1/11/2010 | | DONE |
|
|
|
t/c w shaun at ###-#### - permit ready and fees given
|
Permit Ready to Issue | | | 1/11/2010 | | DONE |
|
|
|
|
Issue and Print Permit | | | 1/11/2010 | | DONE |
|
|
|
|
Application received | | | 1/8/2010 | | |
|
|
|
|