Permit NumberFIR10-00194
StatusFinaled
Name PEAK ALARM
Site Address 4600 S APPLE ST
Project NameMOTIVE POWER-Q-TRON/TRAINING B
Customer Number 
ePlanReview 
Description
This fire alarm permit is to provide a non-required manual fire alarm system in a non-sprinklered building. The system includes an annunciator, a heat detector above the panel, pull stations, full notification, and partial area smoke detection. There is no associated building permit.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  12/2/2010 DONE
Plans taken to records for scanning.
INSP-Final Inspection9/30/201010/5/201010/6/2010APASS
DetailsForrest France
Correction items verified for completion, inspection passed. Fire alarm permit finaled.
Inspection Record Card- Fire8/4/2010 8/4/2010 DONE
DetailsPatricia Smith
Telephone call  8/4/2010 DONE
t/c w ben at ###-#### - permit (plan mod) ready and fees given
Permit Ready to Issue  8/4/2010 DONE
Details
CHANGE STATUS TO (ISS)  8/4/2010 DONE
DetailsTisha Gallop
Plan assigned to (Stephanie)7/30/2010 8/3/2010 DONE
DetailsStephanie L. Cobbley
8/3/2010 15:42:02 SLC - activity updated through activity FIRA24 from case FIR10-00194.
Alarm Plan Check8/3/2010 8/3/2010 PASS
DetailsStephanie L. Cobbley
Plan modificationa approved - see review comments
PLANS TAKEN FRONT DESK ALARM  8/3/2010 DONE
Approved plan modification drawings available at front counter
Plan resubmittals received  7/30/2010 DONE
DetailsTisha Gallop
received application and two coipes of submittal documents and plans; taken to Fire Review
INSP-Final Inspection6/16/20106/17/20106/17/2010AFAIL
DetailsTroy Cobbley
Relocate the two smoke detectors as clouded on the plans so that they do not exceed 15' from any one wall. Resubmit plans showing the correct candella used on the strobes. Resubmit plans that show the correct wire guage used for the notification circuits. Resubmit plans showing the three doors with the mag locks (access controled egress doors). The EOL voltage tested ok and two pull stations tested ok. Phone line troubles and battery troubles were received at the central station. Need to verify the items above and test the smoke detectors and heat detector.
Issue and Print Permit  5/7/2010 DONE
Plan assigned to (Stephanie)4/28/2010 5/6/2010 DONE
DetailsStephanie L. Cobbley
5/6/2010 15:36:15 SLC - activity updated through activity FIRA24 from case FIR10-00194.
1st review completed  5/6/2010 DONE
Alarm Plan Check5/6/2010 5/6/2010 PASS
DetailsStephanie L. Cobbley
Approved - see redlines and review comments
PLANS TAKEN FRONT DESK ALARM  5/6/2010 DONE
approved redlined plans available at front counter
Inspection Record Card- Fire5/6/2010 5/6/2010 DONE
DetailsPatricia Smith
Telephone call  5/6/2010 DONE
t/c w ben at ###-#### - permit ready and fees given
Permit Ready to Issue  5/6/2010 DONE
Details
Application received  4/28/2010