Case Summary | | | 4/23/2014 | | |
|
|
|
|
INSP-Final Inspection | 4/8/2014 | 4/9/2014 | 4/9/2014 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Sprinkler Rough-in/Hydro | 3/26/2014 | 3/27/2014 | 3/27/2014 | A | FAIL |
Troy Cobbley
|
|
|
Need to provide a Knox Box as per the approved plans and discussion. Need to make the monitoring account "live".
|
Plan assigned to (Lee) | 3/26/2014 | | 3/26/2014 | | DONE |
Lee G Meredith
|
|
|
Plan Modification Received.
|
Alarm Plan Check | 3/26/2014 | | 3/26/2014 | | PASS |
Lee G Meredith
|
|
|
FACP, detector and modules relocated.
|
PLANS TAKEN FRONT DESK ALARM | | | 3/26/2014 | | DONE |
|
|
|
Approved plan modification includes relocation of fire alarm panel, related smoke detector and modules.
|
(F) Reprint permit | | | 3/26/2014 | | DONE |
|
|
|
|
CHANGE STATUS TO (ISS) | | | 3/26/2014 | | DONE |
Tisha Gallop
|
|
|
plan mod
|
Plan resubmittals received | | | 3/25/2014 | | |
|
|
|
Reeived 1 copy of FA-1, FA-2, FA-3 and given to Lee
|
INSP-Sprinkler Rough-in/Hydro | 3/7/2014 | 3/13/2014 | 3/13/2014 | A | FAIL |
Troy Cobbley
|
|
|
No city approved plans on site, if shop drawings match city approved resumittal are required showing the changes. Smoke detectors are too close to grills, candellas on strobes are not set correctly, strobes are overspace even if set correctly. FACP has been relocated. Manual pull station has been relocated. No test form provided. No sigal report provided. No test was performed.
|
Permit Ready to Issue | | | 1/28/2014 | | DONE |
Barbara Stitt
|
|
|
|
Issue and Print Permit | | | 1/28/2014 | | DONE |
Barbara Stitt
|
|
|
|
Inspection Record Card- Fire | 1/28/2014 | | 1/28/2014 | | DONE |
Barbara Stitt
|
|
|
|
Plan assigned to (Lee) | 1/23/2014 | | 1/23/2014 | | DONE |
Lee G Meredith
|
|
|
|
1st review completed | | | 1/23/2014 | | PASS |
|
|
|
|
Alarm Plan Check | 1/23/2014 | | 1/23/2014 | | PASS |
Lee G Meredith
|
|
|
|
PLANS TAKEN FRONT DESK ALARM | | | 1/23/2014 | | DONE |
|
|
|
Plans approved. ProjectDox updated.
|
Application received | | | 1/22/2014 | | DONE |
|
|
|
Application submitted via PDS Online on Jan 22 2014 12:53PM
|