DOC - Permit Finaled | 2/13/2002 | 2/13/2002 | 2/13/2002 | A | PASS |
Rick Jackson
|
|
|
Finaled by inspector at 2/13/2002 10:24:48 AM
|
INSP-Sprinkler Rough-in/Hydro | 2/7/2000 | 2/8/2000 | 2/8/2000 | A | 409 |
Rick Jackson
|
|
|
Todd ###-#### Hydro only
|
INSP-Final Inspection | 2/1/2000 | 2/2/2000 | 2/2/2000 | P | FAIL |
Rick Jackson
|
|
|
Todd ###-#### sprinkler pipe damaged prior to inspection; can't test until pipe is repaired
|
INSP-Sprinkler Rough-in | 12/2/1999 | 12/6/1999 | 12/6/1999 | A | PASS |
Rick Jackson
|
|
|
TODD ###-#### Ok to cover.
|
INSP-Conference | 10/29/1999 | 11/2/1999 | 11/2/1999 | A | PART |
Rick Jackson
|
|
|
###-#### With contractor about addressing; PIV for sprinklers (not installed- will use 1hr room)
|
INSP-Sprinkler Rough-in | 11/2/1999 | 11/2/1999 | 11/2/1999 | A | FAIL |
Rick Jackson
|
|
|
hangers no installed at end of pipe in all areas. Spacing of hagers at elbows incorrect.
|
Inspection Record Card- Bld | 10/28/1999 | 10/28/1999 | 10/28/1999 | | DONE |
|
|
|
|
Telephone call | | | 10/28/1999 | | DONE |
|
|
|
called John warnick Commercial Fire ###-####
|
Issue permit | | | 10/28/1999 | | DONE |
|
|
|
|
Fire Sprinkler Plan Check | | | 10/27/1999 | | PASS |
|
|
|
|
Plans/Appl Taken to Front Desk | | | 10/27/1999 | | PASS |
|
|
|
|
Application received | | | 10/15/1999 | | PASS |
|
|
|
|
Case Summary | | | | | |
|
|
|
|