DOC - Permit Finaled | 2/13/2002 | 2/13/2002 | 2/13/2002 | A | PASS |
Rick Jackson
|
|
|
Finaled by inspector at 2/13/2002 9:18:55 AM
|
INSP-Sprinkler Rough-in/Hydro | 5/5/2000 | 5/5/2000 | 5/5/2000 | A | FAIL |
Rick Jackson
|
|
|
overspacing; cages for heads under stairs; lighting room needs additional head; 2nd floor by stair head within 4 inches of wall; calc and FM tag on riser; high temp head needed near heater on 2nd floor
|
INSP-Supply line flush | 4/26/2000 | 4/26/2000 | 4/26/2000 | P | PASS |
Rick Jackson
|
|
|
flush okay
|
INSP-Sprinkler Rough-in/Hydro | 4/11/2000 | 4/11/2000 | 4/11/2000 | P | PART |
Rick Jackson
|
|
|
basement area requires in concealed space under stairs at west end
|
INSP-Sprinkler Rough-in | 4/3/2000 | 4/3/2000 | 4/3/2000 | A | PART |
Rick Jackson
|
|
|
okay to cover music instruction rooms on north side only. cavity to be filled to keep concealed space under 6 inches. heads overspaced at tmep wall on 2nd floor.
|
Sprinkler Plan Check | 1/14/2000 | | 2/4/2000 | | PASS |
|
|
|
Provided calculations and modified piping for basement storage area to meet Ordinary Group 2 Hazard.
|
Miscellaneous action | | | 2/4/2000 | | PASS |
|
|
|
Basement modified piping and calculation plans taken to the front desk for calling and distribution.
|
INSP-Supply line flush | 1/26/2000 | 1/26/2000 | 1/26/2000 | | PASS |
Rick Jackson
|
|
|
this is to update the records - supply line cover and flush conducted a few months ago. both pass.
|
INSP-Sprinkler Rough-in/Hydro | 1/25/2000 | 1/25/2000 | 1/25/2000 | P | PART |
Rick Jackson
|
|
|
underground hydro okay
|
Inspection Record Card- Bld | 12/23/1999 | 12/23/1999 | 12/23/1999 | | DONE |
|
|
|
|
Telephone call | | | 12/23/1999 | | DONE |
|
|
|
talked to brad kilburn to verify plans are ready
|
Issue permit | | | 12/23/1999 | | DONE |
|
|
|
|
Sprinkler Plan Check | 12/22/1999 | | 12/22/1999 | | PASS |
|
|
|
|
Sprinkler Plan Check | 12/22/1999 | | 12/22/1999 | | PASS |
|
|
|
|
Miscellaneous action | | | 12/22/1999 | | PASS |
|
|
|
PLANS TAKEN TO THE FRONT DESK FOR PERMITTING
|
Telephone call | | | 12/13/1999 | | FAIL |
|
|
|
CONTACTED BRAD KILBURN CONCERNING PLAN ELIGIBLE
|
Sprinkler Plan Check | 12/8/1999 | | 12/13/1999 | | FAIL |
|
|
|
CANNOT READ PLANS CLEARLY FOR A REVIEW
|
Application received | | | 12/8/1999 | | PASS |
|
|
|
WATER SUPPLY PROVIDED BY UNITED WATER, THROUGH WHITE LEISURE CONSTRUCTION, FROM CARTER SOMMERSET.
|
INSP-Final Inspection | 11/22/1999 | 11/22/1999 | 11/22/1999 | A | DONE |
Rick Jackson
|
|
|
|
Case Summary | | | | | |
|
|
|
|