MEC-Aging Inspection | 10/29/2001 | 10/29/2001 | 10/29/2001 | | PASS |
Alan Hauser
|
|
|
|
DOC - Permit Finaled | 10/29/2001 | 10/29/2001 | 10/29/2001 | A | PASS |
Alan Hauser
|
|
|
Finaled by inspector at 10/29/2001 8:48:46 AM
|
Pressure Test | 8/27/2001 | 8/28/2001 | 8/28/2001 | A | CANC |
Alan Hauser
|
|
|
wanted final 8/28/2001 12:58:43 PM
|
Final | 8/28/2001 | 8/28/2001 | 8/28/2001 | P | PASS |
Alan Hauser
|
|
|
Added by Inspector: 350 On 8/28/2001 12:59:02 PM
|
Final | 8/21/2001 | 8/21/2001 | 8/21/2001 | P | FAIL |
Alan Hauser
|
|
|
Added by Inspector: 350 On 8/21/2001 12:27:32 PM gasline undersized at rtu, raise regulator vent
|
Pressure Test | 7/6/2001 | 7/6/2001 | 7/6/2001 | A | PASS |
Alan Hauser
|
|
|
Scheduled by a contractor via Hello! on 07/06/2001 at 07:26:34. Contact: ###-####.
|
Pressure Test | 7/5/2001 | 7/5/2001 | 7/5/2001 | P | FAIL |
Alan Hauser
|
|
|
one test 20# for two furnaces pasted, one 20# for heaters failed, and mainline test gage bad, back plate bent and wouldn't let needle move as air was let out. 7/5/2001 1:31:52 PMat 12:30 pressure was on 58#, told to pump up and would come back, at 1:15 looked at gage and back plate was bent to hold needle. talked to henry, and request new inspection 7/5/2001 1:33:55 PM
|
Rough-in | 7/2/2001 | 7/3/2001 | 7/3/2001 | A | NR |
Alan Hauser
|
|
|
###-####
|
Pressure Test | 7/2/2001 | 7/3/2001 | 7/3/2001 | A | NR |
Alan Hauser
|
|
|
need to go to a 5# system to make system work 7/3/2001 9:29:02 AM
|
Pressure Test | 7/2/2001 | 7/2/2001 | 7/2/2001 | P | FAIL |
Alan Hauser
|
|
|
no engineered plans on site for inspection, this a 2# system 7/2/2001 1:17:37 PM
|
MEC-Aging Inspection | 6/14/2001 | 6/14/2001 | 6/14/2001 | | PASS |
Dixie Fellows
|
|
|
work in progress 6/14/2001 1:14:50 PM
|
Application received | | | 3/15/2001 | | |
|
|
|
|
Issue & PRINT permit | | | 3/15/2001 | | DONE |
|
|
|
|