Final | 4/11/2011 | 4/12/2011 | 4/12/2011 | A | PASS |
Alan Hauser
|
|
|
|
Pressure Test | 3/18/2011 | 3/18/2011 | 3/18/2011 | P | PASS |
Alan Hauser
|
|
|
60# on gasline to bbq
|
Rough-in | 3/17/2011 | 3/18/2011 | 3/18/2011 | A | FAIL |
Alan Hauser
|
|
|
gasline still not buried 8" below concrete to be poured
|
Pressure Test | 3/16/2011 | 3/17/2011 | 3/17/2011 | A | FAIL |
Alan Hauser
|
|
|
gasline laying on top of ground
|
Rough-in | 3/15/2011 | 3/16/2011 | 3/16/2011 | A | FAIL |
Alan Hauser
|
|
|
buried gasline has to be 12" below grade even when under concrete walkway
|
MEC-Aging Inspection | 2/28/2011 | 2/28/2011 | 2/28/2011 | | CANC |
Alan Hauser
|
|
|
|
Pressure Test | 12/23/2010 | 12/27/2010 | 12/27/2010 | A | PASS |
Troy James
|
|
|
JOB CONTACT IS AB ###-#### Phone #: ###-#### >> Inspection requested via web by MARGGIE BUSS 60# test
|
MEC-Aging Inspection | 12/1/2010 | 12/1/2010 | 12/1/2010 | | CANC |
Alan Hauser
|
|
|
|
Application received | | | 9/1/2010 | | DONE |
|
|
|
This permit was created on the web by ADAM WARR
|
First Notice | 4/12/2011 | 4/12/2011 | | | |
Alan Hauser
|
|
|
|