Final | 2/2/2017 | 2/2/2017 | 2/2/2017 | P | PASS |
Ben Livingston
|
|
|
Oleg-please call Oleg for access Phone #: ###-####
|
Final | 12/29/2016 | 12/30/2016 | 12/29/2016 | A | CANC |
Ben Livingston
|
|
|
Phone #: ###-#### >> Inspection requested via web by Oleg Chervak Inspection cancelled from web by: Oleg Chervak
|
Conference | 8/31/2016 | 9/1/2016 | 9/1/2016 | A | PASS |
Ben Livingston
|
|
|
Phone #: ###-#### Inspection requested via web by Oleg Chervak
|
Rough-in | 9/1/2016 | 9/1/2016 | 9/1/2016 | P | PASS |
Ben Livingston
|
|
|
Phone #: ###-#### Inspection requested via web by Oleg Chervak
|
Rough-in | 8/30/2016 | 8/30/2016 | 8/30/2016 | P | NR |
Ben Livingston
|
|
|
Oleg Phone #: ###-####
|
Rough-in | 8/26/2016 | 8/29/2016 | 8/29/2016 | A | FAIL |
Ben Livingston
|
|
|
Oleg Phone #: ###-####- add pipe to your taps so 26 gage pipe extends through the fire rated cieling. pipe also needs to be insulated
|
Rough-in | 8/24/2016 | 8/24/2016 | 8/24/2016 | P | FAIL |
Ben Livingston
|
|
|
Oleg Phone #: ###-####- need to run duct in garage per manual j all garage penatrations need to be 26 gage mtl and fire caulked. cannot have wire in a return plenum
|
Pressure Test | 8/22/2016 | 8/23/2016 | 8/24/2016 | A | PASS |
Ben Livingston
|
|
|
Oleg Phone #: ###-####- 20lb gas pass, 5lb flue
|
Rough-in | 8/22/2016 | 8/23/2016 | 8/23/2016 | A | FAIL |
Ben Livingston
|
|
|
Oleg Phone #: ###-#### wrong manual j
|
Issue PAID IN FULL permit | | | 8/10/2016 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 8/10/2016 | | DONE |
|
|
|
This permit was created on the web by Oleg Chervak
|