DOC - Permit Finaled | | | 3/29/2010 | | DONE |
|
|
|
change status to FNL
|
(F) Reprint permit | | | 3/19/2010 | | DONE |
|
|
|
|
CHANGE STATUS TO (COL) | | | 3/19/2010 | | DONE |
|
|
|
|
Final | 3/11/2009 | 3/11/2009 | 3/11/2009 | P | PASS |
Jim Johnson
|
|
|
|
Final | 3/10/2009 | 3/10/2009 | 3/10/2009 | P | PART |
Jim Johnson
|
|
|
Guy Phone #: ###-#### need to install atomspheric vacuum breaker,s on beauty sink,s for final
|
Final | 3/6/2009 | 3/6/2009 | 3/6/2009 | P | PART |
Jim Johnson
|
|
|
guy Phone #: ###-#### made walk through with plumbing contractor need to provide open front seat,s on water closet,s need to provide 120 degree hot water limitation to public lave upc 414.1 need one inch air gap on condensate line at mop sink need to install atomspheric vacuum breakers on beauty sink,s contractor to recall when ready
|
PLM-Aging Inspection | 1/28/2009 | 1/28/2009 | 1/28/2009 | | PASS |
Jim Johnson
|
|
|
under construction
|
Plumbing Rough-in | 11/25/2008 | 11/25/2008 | 11/25/2008 | P | PASS |
Jim Johnson
|
|
|
Guy- late PM please Phone #: ###-####
|
Other | 11/14/2008 | 11/17/2008 | 11/17/2008 | A | PART |
Jim Johnson
|
|
|
Guy- conference Phone #: ###-#### conf. only
|
Application received | | | 11/14/2008 | | |
|
|
|
|
Issue & PRINT permit | | | 11/14/2008 | | DONE |
Alexandra L. DeYoung
|
|
|
|
First Notice | 3/11/2009 | 3/11/2009 | | | |
Jim Johnson
|
|
|
|