Inspections for the day of: Wednesday, October 18, 2006.
Number of inspections: 17
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-02669 ELE-Aging Inspection10/18/200610/18/200610/20/2006 11:04:57 AM DONE
see final
ELE06-01280 ELE-Aging Inspection10/18/200610/18/200610/20/2006 10:56:06 AM PASS
ok to final
ELE06-02424 Final10/18/200610/18/200610/18/2006 4:00:08 PMPPASS
tyler - note: call 1/2 prior to going out ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ok to final
ELE06-03742 Electrical Rough-In10/18/200610/18/200610/18/2006 3:57:37 PMPFAIL
randy - note: ceiling ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith called left corr notice, nec 330.30(B) mc shall be strapped within 12" of box, 348.30(A) fmc shall be strapped within 12" of box, 110.12(A) unused openings in boxes shall be closed, 300.31 box covers shall be installed, BCC fixtures shall be secured in place with minimum 2 support wires, BCC no violation shall be retained
ELE06-02993 Final10/17/200610/18/200610/18/2006 3:01:45 PMAPASS
OUR CONTRACT IS COMPLETE; SOMEONE ELSE WILL HAVE TO GET A PERMIT IN FUTURE WHEN THE BUILGING AROUND POOL EQUIPMENT IS BUILT ; Phone #: ###-#### Internet Inspection Request from: Lee VanSchoiack ok to final, called left message to strap rnc,
ELE06-03862 Permanent Service10/18/200610/18/200610/18/2006 2:41:36 PMPPASS
inspection on 200amp service upgrade and circuit for jetted tub and repalce exhaust fans. will be ready late this afternoon call Tate @###-#### Internet Inspection Request from: Andy Rose p/s o/h n ok
ELE06-03814 Rough-In Permanent Service10/18/200610/18/200610/18/2006 2:16:19 PMPPASS
kevin; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles p/s o/h rec ok
ELE04-00305 Final10/16/200610/18/200610/18/2006 1:55:05 PMPPASS
chuck ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith corrections made, ok to final
ELE06-02104 Electrical Rough-In10/17/200610/18/200610/18/2006 1:26:07 PMPFAIL
Mike should be on site if not please call with any questions or call Don ###-#### Thanks; Phone #: ###-#### Internet Inspection Request from: Don Lustig called, left corr notice, nec 348.30 (A) fmc shall be supported within 12" of boxes
ELE06-03252 Final10/17/200610/18/200610/18/2006 10:58:56 AMAPASS
andry; Phone #: ###-#### Internet Inspection Request from: Patricia Smith told owner to put cover plate on receptacle and move light switch for rear door, ok to final
ELE06-03833 Electrical Rough-In10/17/200610/18/200610/18/2006 10:57:40 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Phil Baker ric ok
ELE06-03856 Final10/17/200610/18/200610/18/2006 10:20:54 AMAPASS
jessie; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ok to final
ELE06-03859 Electrical Rough-In10/17/200610/18/200610/18/2006 9:46:56 AMAFAIL
Call Luke the leadman if this fails inspection, Thank you!; Phone #: ###-#### Internet Inspection Request from: KATHY WEIL called, left corr notice, nec 312.5 all conductors entering enclosures shall have abrasion protection, 300.4(A)&(D) edge of bored holes and nm cable shall be 1 1/4" from edge of framing members, BCC all make-up shall be done
ELE06-02811 Final10/17/200610/18/200610/18/2006 9:38:00 AMAFAIL
Scheduled by a contractor via Hello! on 10/17/2006 at 9:50:06 PM. Contact: ###-####. left corr notice, told owner, nec 406.8 in-use cover shall be installed outside in wet area, 406.5 faceplates shall seat against mounting surfaces, 408.4 panel cover shall be installed and circuit directory shall be complete concise and explicit, for each circuit, 422.31 disconnect shall be installed for hot water heater, 210.8(A) gfci shall operate in bath and outside, 348.30 fmc shall be securely fastened within 12" of box
ELE06-02178 Electrical Rough-In10/17/200610/18/200610/18/2006 9:04:52 AMAPART
Scheduled by a contractor via Hello! on 10/17/2006 at 11:16:22 AM. Contact: ###-####. exterior perimeter lighting only ok to cover
ELE06-03337 Final10/17/200610/18/200610/18/2006 8:53:44 AMAPASS
pat; Phone #: ###-#### note: #64 Internet Inspection Request from: Patricia Smith corr made, ok to final
ELE06-03628 Final10/18/200610/18/200610/18/2006 8:39:20 AMAPASS
Scheduled by a contractor via Hello! on 10/18/2006 at 5:47:17 AM. Contact: ###-####. ok to final