ELE-Aging Inspection | 6/25/2008 | 6/25/2008 | 7/1/2008 | | DONE |
Bob Reichert
|
|
|
see final
|
Final | 7/1/2008 | 7/1/2008 | 7/1/2008 | A | PASS |
Bob Reichert
|
|
|
ok to final, no esc for project
|
Final | 12/29/2006 | 1/2/2007 | 1/2/2007 | A | PART |
Bob Reichert
|
|
|
Jack; Phone #: ###-#### Internet Inspection Request from: Sherri Bennett called contr, owner lv not corrected, contr needs to strap mc cable, will call after rest of lv people get done with security etc
|
Final | 12/29/2006 | 12/29/2006 | 12/29/2006 | P | NR |
Bob Reichert
|
|
|
Jack; Phone #: ###-#### Internet Inspection Request from: Sherri Bennett corrections not made, not ready for inspection
|
Final | 12/28/2006 | 12/28/2006 | 12/28/2006 | P | FAIL |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: Tollie Rogers corr fee due posted called,110.12(A) seal all KOs, 314.25 install covers all boxes, 400.8 shall not use cords for fixed wiring shall not be above ceilings and shall remove recept from above ceiling, correction posted to bld06-03430 for all low voltage remove all abandonded cables shall support all cables, cables shall not lay on grid
|
Final | 12/26/2006 | 12/26/2006 | 12/26/2006 | P | PART |
Pat Lass
|
|
|
This is to cover the drop ceiling.; Phone #: ###-#### Internet Inspection Request from: Tollie Rogers ceiling ok to cover except by exit light that requires support for box and fixture whip changed out for mc cable. no final at this time.
|
Final | 12/21/2006 | 12/22/2006 | 12/22/2006 | A | NR |
Bob Reichert
|
|
|
Tollie; Note: please call 1/2 before insp; Phone #: ###-#### Internet Inspection Request from: Sherri Bennett called about ko's, recpts in clg, pnl schedule, strap mc
|
Electrical Rough-In | 12/15/2006 | 12/15/2006 | 12/15/2006 | P | PART |
Jack Frank
|
|
|
tolly - ###-#### walls only
|