Information based on query as of Sunday, January 18, 2026.
Permit Information
Permit NumberELE07-03307
StatusFinaled
Name TRI-STATE ELECTRIC
Site Address 851 W FRONT ST
Project NameTHE ASPEN
Customer Number 
ePlanReview 
Description
Electrical Permit - New: new construction of the Aspen Lofts
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
First Notice3/23/20093/23/20092/11/2014 DONE
DetailsBob Reichert
This permit finaled on the web by Deb Gooden
Second Notice ELE3/3/20093/3/20092/11/2014 DONE
DetailsJim Toombs
This permit finaled on the web by Deb Gooden
Final3/19/20093/23/20093/23/2009APASS
DetailsBob Reichert
CONTACT: NEIL RAMSEY Phone #: ###-#### Internet Inspection Request from: Deb Gooden core and shell ok to final basement thru 9th floor plus 9th floor condos, signed structural card
Electrical Rough-In3/18/20093/19/20093/19/2009APART
DetailsBob Reichert
Contact: Neil Ramsey - Ceiling inspection in the Fire Command Room and Partial final for the shell & core please. Phone #: ###-#### Internet Inspection Request from: Deb Gooden ok to cover ceiling fire riser room, part final floors 10 thru roof ok anop
Electrical Rough-In3/5/20093/9/20093/9/2009PPASS
DetailsBob Reichert
Contact: Neil Ramsey - Ceiling inspections for floors 14,15,16, & 17 hallways please Phone #: ###-#### Internet Inspection Request from: Deb Gooden ceilings only ok to cover floor hall 14, 15, 16, 17 anop
Electrical Rough-In3/2/20093/3/20093/3/2009PPASS
DetailsBob Reichert
Contact: Neil Ramsey - Ceiling inspection 10 thru 12 hallways please Phone #: ###-#### Internet Inspection Request from: Deb Gooden ok to cover ceilings floor 1, 10, 11, 12 anop
First Notice1/8/20091/8/20093/3/2009 DONE
DetailsBob Reichert
Electrical Rough-In2/24/20092/26/20092/26/2009APASS
DetailsBob Reichert
Contact: Neil Ramsey - Fire Command room inspection please Phone #: ###-#### Internet Inspection Request from: Deb Gooden walls only ok to cover fire command room anop
Electrical Rough-In2/18/20092/19/20092/19/2009APASS
DetailsBob Reichert
Contact: Neil Ramsey - Ceiling inspection, 9th floor hallway please Phone #: ###-#### Internet Inspection Request from: Deb Gooden ok to cover 9th floor ceiling only anop
Electrical Rough-In1/28/20091/28/20091/28/2009PPASS
DetailsBob Reichert
Contact: Neil Ramsey - 4th Floor Maintenance & 3rd Floor generator areas. Phone #: ###-#### Internet Inspection Request from: Deb Gooden ok to cover 3rd floor generator room and 4th floor maintenance room
Electrical Rough-In1/22/20091/26/20091/26/2009APASS
DetailsBob Reichert
Contact Neil Ramsey. Rough-in inspection 1st floor ceiling. Also, 6th and 7th floor ceiling inspections. Phone #: ###-#### Internet Inspection Request from: Shelli Daylong 1st floor west soffit and 7th floor ceiling ok to cover
Electrical Rough-In1/20/20091/21/20091/21/2009PPASS
DetailsBob Reichert
Contact: Neil Ramsey - floors 15,16 & 17 hallways please Phone #: ###-#### Internet Inspection Request from: Deb Gooden 15, 16, 17 halls ok to cover, 6th floor ceiling ok to cover
Electrical Rough-In1/14/20091/15/20091/15/2009PPASS
DetailsBob Reichert
Contact: Neil Ramsey. Rough-in inspection of: Elevator Fronts floors 14-18; Elevator Fronts basement & 1st floor; Elevator Lobby rough-in walls. Early afternoon if at all possible. Phone #: ###-#### Internet Inspection Request from: Shelli Daylong elevator fronts - basement, 1, 14,15,16,17,18, 1st floor lobby only ok to cover
Electrical Rough-In1/12/20091/13/20091/13/2009APASS
DetailsBob Reichert
Contatc: Neil Ramsey - soffit recessed lights 1st floor and elevator fronts 3rd & 4th floors please Phone #: ###-#### Internet Inspection Request from: Deb Gooden 1st floor soffits, 3&4th floor elevator fronts ok to cover
Change Status to I  1/12/2009  
My mistake was finaled by bob was on the floors only
Final1/7/20091/8/20091/8/2009PPASS
DetailsBob Reichert
Contact: Neil Ramsey - 5th floor ceiling inspection and 2nd floor elevator fronts rough-in please Phone #: ###-#### Internet Inspection Request from: Deb Gooden ric ok 2nd floor elevator front, 5th floor ceiling
Final1/5/20091/6/20091/6/2009ACANC
DetailsBob Reichert
Contact: Neil Ramsey - Rough-in elevator fronts 9,10,11 & 12 Phone #: ###-#### Internet Inspection Request from: Deb Gooden wrong type request, see ri
Electrical Rough-In1/6/20091/6/20091/6/2009APASS
DetailsBob Reichert
Contact: Neil Ramsey - Rough-in elevator fronts 9,10,11 & 12 Phone #: ###-#### Internet Inspection Request from: Deb Gooden ok to cover elevator fronts floor 9, 10, 11, and 12
Electrical Rough-In12/30/200812/31/200812/31/2008PPASS
DetailsBob Reichert
Contact: Neil Ramsey - 6th & 7th floor elevator fronts, 17th floor stairway landing, and hallway on 12th floor. Phone #: ###-#### Internet Inspection Request from: Deb Gooden ok to cover 17th floor stairway, 12th floor hall, 6th, 7th, 8th floor elevator fronts
Electrical Rough-In12/19/200812/22/200812/22/2008PPASS
DetailsBob Reichert
Contact: Neil Ramsey - Rough-in insp. 9,10 & 11th floor hallways please Phone #: ###-#### Internet Inspection Request from: Deb Gooden core and shell interior corridors for 9, 10, and 11th floors ok to cover
Electrical Rough-In12/3/200812/4/200812/4/2008PPASS
DetailsBob Reichert
Contact Neil Ramsey. Rough in inspection 9th Floor Condos 901-907 Phone #: ###-#### Internet Inspection Request from: Shelli Daylong ok to cover 9th floor room walls only
Electrical Rough-In11/17/200811/18/200811/18/2008APASS
DetailsBob Reichert
Contact: Neil Ramsey - 1st floor exit driveway ceiling inspection please Phone #: ###-#### Internet Inspection Request from: Deb Gooden 1st foor ceiling with heaters at drive and stairwell north side ok to cover
Rough-In Permanent Service10/27/200810/27/200810/27/2008PCANC
DetailsBob Reichert
Contact Neil Ramsey. Rough-in for floors 15-18 stairwells East and West. Phone #: ###-#### Internet Inspection Request from: Shelli Daylong wrong type request, see ri
Electrical Rough-In10/27/200810/27/200810/27/2008PPASS
DetailsBob Reichert
Contact Neil Ramsey. Rough-in for floors 15-18 stairwells East and West. Phone #: ###-#### Internet Inspection Request from: Shelli Daylong ri ok 15th thru 18th stairwells east and west side
Electrical Rough-In10/14/200810/15/200810/15/2008PPASS
DetailsBob Reichert
Contact: Neil Ramsey 10th thru 14th floors East & West Stairwells please Phone #: ###-#### Internet Inspection Request from: Deb Gooden stairwells floor 10 to 14 east and west ok to cover
Electrical Rough-In10/8/200810/8/200810/8/2008PPASS
DetailsBob Reichert
CONTACT: NEIL RAMSEY - ABOVE CEILING INSPECTION FOR THE EAST PORTION OF 4TH FLOOR Phone #: ###-#### Internet Inspection Request from: Deb Gooden ok to cover 4th floor floor ceilings
Electrical Rough-In9/18/20089/18/20089/18/2008PPART
DetailsBob Reichert
Contact Neil Ramsey. Rough-in Ceiling inspection 4th floor. Phone #: ###-#### Internet Inspection Request from: Shelli Daylong west 1/2 ceiling only ok to cover
Permanent Service9/11/20089/12/20089/12/2008APASS
DetailsBob Reichert
CONTACT: NEIL RAMSEY Phone #: ###-#### Internet Inspection Request from: Deb Gooden p/s u/g n ok, 1 meter only, could not add esc response
Conference9/8/20089/9/20089/9/2008ADONE
DetailsBob Reichert
CONTACT: PHIL BASSICK Phone #: ###-#### Internet Inspection Request from: Deb Gooden reviewed plans, talked with contractor, ok to use 1 meter per sub-panel per space for residences, main service is delivered at main point by ipco
Conference9/4/20089/5/20089/5/2008ADONE
DetailsBob Reichert
Contact: Phil Bassick, would like to meet at job site about 10:30 if possible. please call before going Phone #: ###-#### Internet Inspection Request from: Deb Gooden met contractor to get copy of one-line to review service for condos
Electrical Rough-In8/27/20088/27/20088/27/2008PPASS
DetailsBob Reichert
Contact Neil Ramsey. 9th Floor stairwell East & West Phone #: ###-#### Internet Inspection Request from: Shelli Daylong ok to cover 9th loor stairwells, east and west, can't add esc inspection
Electrical Rough-In8/22/20088/25/20088/25/2008APASS
DetailsBob Reichert
CONTACT: NEIL RAMSEY, ROOF DECK INSPECTION, LATE MORNING IF POSSIBLE. Phone #: ###-#### Internet Inspection Request from: Deb Gooden ok to pour roof, 18th foor only, can't add esc response
Electrical Rough-In8/8/20088/11/20088/11/2008PPASS
DetailsBob Reichert
Contact Neil Ramsey. Rough-in 18th floor deck. Phone #: ###-#### Internet Inspection Request from: Shelli Daylong ok to pour 18th floor only, can't enter esc data
Electrical Rough-In7/24/20087/24/20087/24/2008PPASS
DetailsBob Reichert
Contact: Neil Ramsey - 17th floor deck and 8th floor East & West stairwells rough-in please.. Early afternoon if possible. Phone #: ###-#### Internet Inspection Request from: Deb Gooden ok to cover 17th floor deck and 8th floor stairwells only
Electrical Rough-In7/23/20087/24/20087/24/2008PCANC
DetailsBob Reichert
Contact: Neil Ramsey - 17th floor deck roughin please. Early afternoon if possible Phone #: ###-#### Internet Inspection Request from: Deb Gooden Inspection cancelled from web by: Deb Gooden
Electrical Rough-In7/17/20087/18/20087/18/2008APART
DetailsPat Lass
Contact: Neil Ramsey - rough in inspection, 1st floor exit stairwells both East and West please Phone #: ###-#### Internet Inspection Request from: Deb Gooden
1st floor exit stairwells both East and West ok
Electrical Rough-In7/9/20087/10/20087/10/2008PPASS
DetailsBob Reichert
contact-Neil Ramsey 16th floor deck area Phone #: ###-#### Internet Inspection Request from: Deb Gooden ok to pour 16th floor
Electrical Rough-In6/23/20086/24/20086/24/2008APASS
DetailsBob Reichert
Contact: Neil Ramsey Rough-in 5th floor hallway and 2nd floor bathrooms please. Phone #: ###-#### Internet Inspection Request from: Deb Gooden2nd floor baths and 5th floor hall ok to cover
Electrical Rough-In6/17/20086/17/20086/17/2008PPASS
DetailsBob Reichert
Contact Neil Ramsey. Inspection of 15th floor deck. Early afternoon if at all possible. Phone #: ###-#### Internet Inspection Request from: Shelli Daylong ok to pour 15th floor
Electrical Rough-In6/4/20086/5/20086/5/2008APASS
DetailsBob Reichert
Contact Neil Ramsey. Rough-in inspection 14th floor deck. Phone #: ###-#### Internet Inspection Request from: Shelli Daylong ok to pour 14th floor
Electrical Rough-In6/3/20086/4/20086/4/2008PPART
DetailsBob Reichert
Contact Neil Ramsey. Rough-inspection of 3rd through 7th floors stairwell walls Phone #: ###-#### Internet Inspection Request from: Shelli Daylong stairwells floors 2 thru 7 only ok to cover, both ends
Electrical Rough-In5/23/20085/27/20085/27/2008APASS
DetailsBob Reichert
Contact Neil Ramsey.12th Floor Deck rough-in inspection. Late moring inspection, if possible. Phone #: ###-#### Internet Inspection Request from: Shelli Daylong 12th floor deck ok to pour, walls only anop ok to cover
Electrical Rough-In5/9/20085/12/20085/12/2008APART
DetailsPat Lass
CONTACT: NEIL RAMSEY - ROUGH-IN 11TH FLOOR DECK AREA PLEASE Phone #: ###-#### Internet Inspection Request from: Deb Gooden
11TH FLOOR DECK AREA OK
Electrical Rough-In4/14/20084/15/20084/15/2008APASS
DetailsBob Reichert
Contact: Neil Ramsey - 10th floor rough-in inspection, Late morning if possible Phone #: ###-#### Internet Inspection Request from: Deb Gooden 10th floor only ok to pour
Electrical Rough-In4/4/20084/7/20084/7/2008APASS
DetailsBob Reichert
Contact Neil Ramsey. Morning inspection of 9th floor deck. Pouring is scheduled to begin at noon. Phone #: ###-#### Internet Inspection Request from: Shelli Daylong 9th floor slab ok to pour
Electrical Rough-In3/27/20083/28/20083/28/2008APART
DetailsPat Lass
Contact: Neil Ramsey - Rough-in inspection 8th floor please Phone #: ###-#### Internet Inspection Request from: Deb Gooden
8th floor deck ok
Electrical Rough-In3/14/20083/17/20083/17/2008PPASS
DetailsWilliam E Thomas
Contatc: Neil Ramsey - 7th floor deck area Phone #: ###-#### Internet Inspection Request from: Deb Gooden
. .1. 7th Floor deck ok for cover. .
Electrical Rough-In3/5/20083/6/20083/6/2008PPASS
DetailsBob Reichert
contact - Neil Ramsey rough-in 6th floor please Phone #: ###-#### Internet Inspection Request from: Deb Gooden 6th floor ok to pour, basement walls only for pump room area ok to cover
Electrical Rough-In2/28/20082/29/20082/29/2008APASS
DetailsBob Reichert
CONTACT: NEIL RAMSEY - BASEMENT ROUGH-IN PLEASE Phone #: ###-#### Internet Inspection Request from: Deb Gooden basement walls except 1 wall to be moved ok to cover only
Electrical Rough-In2/22/20082/25/20082/25/2008PPART
DetailsBob Reichert
CONTACT: NEIL RAMSEY - ROUGH IN 5TH FLOOR DECK AREA PLEASE Phone #: ###-#### Internet Inspection Request from: Deb Gooden 5th floor deck ok to pour, reviewed several areas of job for progression, plans still being revised
Electrical Rough-In11/20/200711/21/200711/21/2007PPASS
DetailsBob Reichert
CONTACT: NEIL RAMSEY - UNDERGROUND INSPECTION PLEASE Phone #: ###-#### Internet Inspection Request from: Deb Gooden ok to cover u/g ground conductors that will go to ground bus, generator, water pipe, gear, transformer, etc
Electrical Rough-In11/15/200711/16/200711/16/2007PPART
DetailsBob Reichert
CONTACT: NEIL RAMSEY - UNDERGROUND INSPECTION PLEASE Phone #: ###-#### Internet Inspection Request from: Deb Gooden looked at electrode to be poured under slab, ok to pour
Electrical Rough-In11/5/200711/6/200711/6/2007APASS
DetailsBob Reichert
CONTACT: NEIL RAMSEY - UNDERGROUND INSPECTION PLEASE Phone #: ###-#### Internet Inspection Request from: Deb Gooden ok to cover u/g from service to 1st junction box, told contractor to provide set of plans for inspectors next inspection
Electrical Rough-In10/23/200710/24/200710/24/2007PDONE
DetailsBob Reichert
Contact: Neil Ramsey - U/G conduit inspection please Phone #: ###-#### Internet Inspection Request from: Deb Gooden looked at u/g for utility incoming power, told contractor we don't inspect line side of meter
Application received  9/24/2007 DONE
This permit was created on the web by Deb Gooden