Permit Information
Permit NumberELE19-04702
StatusFinaled
Name CURRENT ELECTRIC COMPANY
Site Address 1014 E JEFFERSON ST
Project Name 
Customer Number 
ePlanReviewNo
Description
Electrical for detached garage, includes 60amp sub panel and underground feed from existing house panel; 4 new circuits, one space heater
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final1/31/20201/31/20201/31/2020PPASS
DetailsJames Ady
Access through alley is the best look for blue tarp, Phone #: ###-#### Inspection requested via web by steve sellers corrections made final ok
Final1/29/20201/30/20201/30/2020AFAIL
DetailsRock A. Hudson
access through alley to garage sliding door to garage should be open Phone #: ###-#### Inspection requested via web by steve sellers 310.16- Minimum size conductor for 60 amp overcurrent device is #6 copper conductor, #8 installed from house to garage.
Electrical Rough-In12/6/201912/6/201912/6/2019PPASS
DetailsJames Ady
Access from alley Phone #: ###-#### Inspection requested via web by steve sellers Garage and Storage above. (Access will need provided to strorage area at final) Rough in ok
Application received  12/6/2019 DONE
This permit was created on the web by steve sellers
Issue PAID IN FULL permit  12/6/2019 DONE