Rough-in | 7/6/2020 | 7/7/2020 | 7/7/2020 | A | PASS |
Brian Scoles
|
|
|
Phone #: ###-#### Inspection requested via web by Gary Reeves- R/I ok- correction made
|
Pressure Test | 7/2/2020 | 7/6/2020 | 7/6/2020 | A | PASS |
Chad Schwendiman
|
|
|
Phone #: ###-#### Inspection requested via web by Gary Reeves - 20lb gas, 5lb flue
|
Rough-in | 7/2/2020 | 7/6/2020 | 7/6/2020 | A | FAIL |
Chad Schwendiman
|
|
|
Phone #: ###-#### Inspection requested via web by Gary Reeves - need approved manual J on site, Need 1" clearance to combustables on b-vent, Insulation shield for b-vent needs to sit down flush on draft stop.
|
Issue PAID IN FULL permit | | | 6/19/2020 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 6/19/2020 | | DONE |
|
|
|
This permit was created on the web by Gary Reeves
|