Information based on query as of Sunday, June 2, 2024.
Permit Information
Permit NumberPLM19-00079
StatusFinaled
Name ANFINSON PLUMBING LLP
Site Address 1003 W MAIN ST
Project NameGood Burger III + The Drop
Customer Number 
ePlanReviewNo
Description
New: Installation of plumbing, waste, grease, vent, water, Condensate, gas piping, insulation of domestic hot and cold water, plumbing fixtures and trim, as per plans dated 8/24/2018 (value engineered). Includes labor, materials, permits as per plumbing plans.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
First Notice3/12/20193/12/20194/23/2019 DONE
DetailsDaryl Spivey
Final3/11/20193/12/20193/12/2019PPASS
DetailsDaryl Spivey
Need final Plumbing/gas inspection tomorrow afternoon. Phone #: ###-#### Inspection requested via web by Sharon Afinson
Pressure Test1/21/20191/22/20191/22/2019APASS
DetailsDaryl Spivey
9AM would be best. Getting a plumbing rough in inspection as well. Phone #: ###-#### Inspection requested via web by Sharon Afinson
60 lb test ok.............ds
Plumbing Rough-in1/21/20191/22/20191/22/2019APASS
DetailsDaryl Spivey
9AM would be best. Phone #: ###-#### Inspection requested via web by Sharon Afinson
Plumbing Rough-in1/17/20191/18/20191/18/2019PFAIL
DetailsEric Strole
Everett Phone #: ###-####-2-flr sinks & mop sink need to go to grease waste per the approved plans. Test on water pass.
Pressure Test1/17/20191/18/20191/18/2019PCANC
DetailsEric Strole
Everett-would like as late as possible Phone #: ###-####
Issue PAID IN FULL permit  1/4/2019 DONE
Payment received via Govolutions
Application received  1/4/2019 DONE
This permit was created on the web by Sharon Afinson