Water and/or Sewer | 7/10/2020 | 7/10/2020 | 7/10/2020 | P | PART |
Daryl Spivey
|
|
|
A water main inspection. Please call Shayne 30 min prior to arrival. ###-####. thank you. Phone #: ###-#### Inspection requested via web by Rhonda Marcum from meter to inside bld........ds
|
Plumbing Rough-in | 6/1/2020 | 6/2/2020 | 6/2/2020 | A | PART |
Daryl Spivey
|
|
|
Water Mains, please call Shayne at least 30 min prior to inspection, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum level 1A water tested ok......level 2 public rr water tested........ds
|
Plumbing Rough-in | 5/28/2020 | 5/28/2020 | 5/28/2020 | P | NR |
Daryl Spivey
|
|
|
Please call Fernando 30 mins. prior to arrival. Fernando: ###-####. Mech. piping inspection. Thank you. Phone #: ###-#### Inspection requested via web by Rhonda Marcum called wrong permit in......ds
|
Storm Drains | 5/18/2020 | 5/18/2020 | 5/18/2020 | P | PART |
Daryl Spivey
|
|
|
Please call/text Shayne at least 30 min prior to inspection, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum
|
Water and/or Sewer | 5/13/2020 | 5/13/2020 | 5/13/2020 | P | CANC |
Daryl Spivey
|
|
|
Please call Shayne at least 30 min prior to inspection, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum
|
Plumbing Rough-in | 5/13/2020 | 5/13/2020 | 5/13/2020 | P | PART |
Daryl Spivey
|
|
|
Please call Shayne at least 30 min prior to inspection, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum RR's 1st, 2nd and 3rd floors west end........ds
|
Storm Drains | 5/13/2020 | 5/13/2020 | 5/13/2020 | P | PART |
Daryl Spivey
|
|
|
Please call Shayne at least 30 min prior to inspection, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum
|
Med/Gas Systems | 5/11/2020 | 5/12/2020 | 5/12/2020 | P | PART |
Daryl Spivey
|
|
|
Please call Shayne at least 30 min prior to inspection, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum 24 hr test ok.........ds
|
Water and/or Sewer | 5/11/2020 | 5/11/2020 | 5/11/2020 | P | CANC |
Daryl Spivey
|
|
|
Please call Shayne at least 30 min prior to inspection, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum
|
Plumbing Rough-in | 5/11/2020 | 5/11/2020 | 5/11/2020 | P | PART |
Daryl Spivey
|
|
|
Please call Shayne at least 30 min prior to inspection, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum venting 1st floor west........ds
|
Med/Gas Systems | 5/11/2020 | 5/11/2020 | 5/11/2020 | P | PART |
Daryl Spivey
|
|
|
Please call Shayne at least 30 min prior to inspection, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum 2nd floor partial....start 24 hr test........ds
|
Water and/or Sewer | 5/6/2020 | 5/6/2020 | 5/6/2020 | P | PART |
Daryl Spivey
|
|
|
Please call/text Shane at least 30 min prior to inspection, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum roof drains, waste and vent 1st floor partial
|
Plumbing Rough-in | 5/4/2020 | 5/4/2020 | 5/4/2020 | P | PART |
Daryl Spivey
|
|
|
Please call Shane at least 30 min prior to inspection, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum waste and vent 1st floor partial.......ds
|
Med/Gas Systems | 4/29/2020 | 4/30/2020 | 4/30/2020 | A | PART |
Daryl Spivey
|
|
|
Please call Shane at least 30 min prior to inspection, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum 24 hr test ok by oxygen bulk storage area.......ds
|
Med/Gas Systems | 4/28/2020 | 4/28/2020 | 4/28/2020 | P | PART |
Daryl Spivey
|
|
|
Shane is sending pictures of the area. Feel free to call/text him if there are any questions, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum 24 hr on med gas, water tested ok. by oxygen tank area......ds
|
Med/Gas Systems | 4/20/2020 | 4/21/2020 | 4/21/2020 | P | PART |
Daryl Spivey
|
|
|
Please call Fernando at least 30 min prior to inspection, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum 24 hr low pressure test ok.........ds
|
Med/Gas Systems | 4/20/2020 | 4/20/2020 | 4/20/2020 | P | PART |
Daryl Spivey
|
|
|
Please call Fernando at least 30 min prior to inspection, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum high pressure ok start 24 hr low pressure......ds
|
Storm Drains | 4/20/2020 | 4/20/2020 | 4/20/2020 | P | PART |
Daryl Spivey
|
|
|
Please call Fernando at least 30 min prior to inspection, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum east side partial.......ds
|
Water and/or Sewer | 4/20/2020 | 4/20/2020 | 4/20/2020 | P | PART |
Daryl Spivey
|
|
|
Please call Fernando at least 30 min prior to inspection, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum water lines out by oxygen storage area..........ds
|
Plumbing Rough-in | 4/20/2020 | 4/20/2020 | 4/20/2020 | P | PART |
Daryl Spivey
|
|
|
Please call Fernando at least 30 min prior to inspection, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum water on 1st and 2nd floor partial........ds
|
Water and/or Sewer | 4/14/2020 | 4/15/2020 | 4/15/2020 | P | PART |
Daryl Spivey
|
|
|
Please call Fernando, he is prepared to send pictures or video call if you would prefer, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum 1st fl waste and vent partial...........ds
|
Water and/or Sewer | 4/3/2020 | 4/3/2020 | 4/3/2020 | P | PART |
Daryl Spivey
|
|
|
Please call Fernando at least 30 min prior to inspection, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum w/v in cooling tower area east property tested ok......need to see if SS or SD..........ds
|
Med/Gas Systems | 4/3/2020 | 4/3/2020 | 4/3/2020 | P | PART |
Daryl Spivey
|
|
|
Please call Fernando at least 30 min prior to inspection, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum 24 hr test on outside by oxygen storage area and 2nd floor area ok....w/v on drain for cooling tower area tested.....ds
|
Groundwork | 4/1/2020 | 4/2/2020 | 4/2/2020 | A | PART |
Daryl Spivey
|
|
|
Please call Fernando at least 30 min prior, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum water only....ds
|
Storm Drains | 4/1/2020 | 4/2/2020 | 4/2/2020 | A | PART |
Daryl Spivey
|
|
|
Please call Fernando at least 30 min prior, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum marked om plan
|
Med/Gas Systems | 4/1/2020 | 4/2/2020 | 4/2/2020 | A | PART |
Daryl Spivey
|
|
|
Please call Fernando at least 30 min prior, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum start 24 hr.......ds
|
Water and/or Sewer | 3/16/2020 | 3/17/2020 | 3/17/2020 | A | CANC |
Daryl Spivey
|
|
|
Please call Fernando at least 30 min prior to inspection, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum
|
Plumbing Rough-in | 3/17/2020 | 3/17/2020 | 3/17/2020 | A | PART |
Daryl Spivey
|
|
|
Please call Fernando at least 30 min prior to inspection, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum W/V west end 3rd floor.....marked on plan..........ds
|
Plumbing Rough-in | 3/12/2020 | 3/13/2020 | 3/13/2020 | A | PART |
Daryl Spivey
|
|
|
Domestic water inspection. Please call prior to arrival. Fernando: ###-#### Phone #: ###-#### Inspection requested via web by Rhonda Marcum water on 2nd and 3rd floor ........rough in done on 2nd floor..........markedm on plans.........ds
|
Water and/or Sewer | 3/9/2020 | 3/10/2020 | 3/10/2020 | A | CANC |
Daryl Spivey
|
|
|
Please call Fernando at least 30 min prior to inspection, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum
|
Plumbing Rough-in | 3/10/2020 | 3/10/2020 | 3/10/2020 | A | PART |
Daryl Spivey
|
|
|
Please call Fernando at least 30 min prior to inspection, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum 3rd floor W/V marked on plan............ds
|
Storm Drains | 2/27/2020 | 2/28/2020 | 2/28/2020 | A | PART |
Daryl Spivey
|
|
|
Please call Fernando at least 30 min prior to inspection, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum water , waste and vent and roof drains.........marked on plans.......ds
|
Water and/or Sewer | 2/20/2020 | 2/21/2020 | 2/21/2020 | A | CANC |
Daryl Spivey
|
|
|
Please call Fernando at least 30 min prior to inspection, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum
|
Plumbing Rough-in | 2/21/2020 | 2/21/2020 | 2/21/2020 | A | PART |
Daryl Spivey
|
|
|
Please call Fernando at least 30 min prior to inspection, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum partial W/V and R/D ...........ds
|
Other | 2/12/2020 | 2/13/2020 | 2/13/2020 | P | PART |
Daryl Spivey
|
|
|
Waste and Vent, please call Fernando at least 30 min prior to inspection, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum w/v and r/d's marked on plans......ds
|
Other | 2/11/2020 | 2/12/2020 | 2/12/2020 | A | CANC |
Daryl Spivey
|
|
|
Waist and Vent, Please call Fernando at least 30 min prior to inspection, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum
|
Plumbing Rough-in | 2/12/2020 | 2/12/2020 | 2/12/2020 | A | PART |
Daryl Spivey
|
|
|
Waist and Vent, Please call Fernando at least 30 min prior to inspection, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum partial W/V on 2nd floor ...........ds
|
Water and/or Sewer | 2/10/2020 | 2/11/2020 | 2/10/2020 | P | CANC |
Daryl Spivey
|
|
|
Please call Fernando at least 30 min prior to inspection, thank you! Phone #: ###-#### >> Inspection requested via web by Rhonda Marcum Inspection cancelled from web by: Rhonda Marcum
|
Plumbing Rough-in | 2/5/2020 | 2/6/2020 | 2/6/2020 | A | PART |
Matt Wrobel
|
|
|
dwv h2o water and waste areas a - d marked portions on print hammer arresters for bathrooms on rfi to engineer/architect
|
Water and/or Sewer | 2/4/2020 | 2/5/2020 | 2/5/2020 | P | PEND |
Dan Ediger
|
|
|
DWV and Domestic Water inspection. Please call Fernando ###-#### 30 minutes prior to arrival. Thank you. Phone #: ###-#### Inspection requested via web by Rhonda Marcum reschduled
|
Water and/or Sewer | 1/21/2020 | 1/21/2020 | 1/21/2020 | P | PASS |
Matt Wrobel
|
|
|
Please call Fernando at least 30 min prior to inspection, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum
|
Med/Gas Systems | 1/7/2020 | 1/8/2020 | 1/8/2020 | P | PART |
Daryl Spivey
|
|
|
Please call Shane at least 30 min prior to inspection, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum 24 hr test on med gas ok...........ds
|
Storm Drains | 1/7/2020 | 1/7/2020 | 1/7/2020 | P | PART |
Daryl Spivey
|
|
|
DWV/ Storm Drain/ Med Gas; Please call Fernando at least 30 min prior to inspection, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum start 24 hr on med gas......rest marked on plans.....ds
|
Plumbing Rough-in | 12/19/2019 | 12/19/2019 | 12/19/2019 | P | PART |
Matt Wrobel
|
|
|
Co inspection with Daryl 2 more sections passed ond marked/signed on prints
|
Med/Gas Systems | 12/18/2019 | 12/19/2019 | 12/19/2019 | P | PART |
Matt Wrobel
|
|
|
24 hour check passed signed on print
|
Water and/or Sewer | 12/18/2019 | 12/19/2019 | 12/19/2019 | P | CANC |
Daryl Spivey
|
|
|
Please call Fernando at least 30 min prior to inspection, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum
|
Plumbing Rough-in | 12/19/2019 | 12/19/2019 | 12/19/2019 | P | PART |
Daryl Spivey
|
|
|
Please call Fernando at least 30 min prior to inspection, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum inspect with Matt.........waste and vent and med gas.......marked on plans......2nd floor east....ds
|
Med/Gas Systems | 12/17/2019 | 12/18/2019 | 12/18/2019 | P | PART |
Matt Wrobel
|
|
|
Please call Fernando at least 30 min prior to inspection, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum start 24 hour test
|
Water and/or Sewer | 12/17/2019 | 12/18/2019 | 12/18/2019 | P | PART |
Matt Wrobel
|
|
|
Please call Fernando at least 30 min prior to inspection, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum areas marked and signed on print
|
Plumbing Rough-in | 12/6/2019 | 12/6/2019 | 12/6/2019 | P | DONE |
Matt Wrobel
|
|
|
Please call Fernando at least 30 min prior to inspection, Rain drain/waste/domestic water. Thank you and stay warm! Phone #: ###-#### Inspection requested via web by Rhonda Marcum walkthru with daryl
|
Water and/or Sewer | 12/5/2019 | 12/6/2019 | 12/6/2019 | P | PART |
Daryl Spivey
|
|
|
Please call Fernando at least 30 min prior to inspection, Rain drain/waste/domestic water. Thank you and stay warm! Phone #: ###-#### Inspection requested via web by Rhonda Marcum walked job with Matt....W/V, water and R/D's....marked on plan.............east side......ds
|
Med/Gas Systems | 11/20/2019 | 11/21/2019 | 11/21/2019 | P | PART |
Daryl Spivey
|
|
|
Please call Fernando at least 30 min prior to inspections, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum 24 hr test ok on areas tested and marked on plan...........ds
|
Plumbing Rough-in | 11/19/2019 | 11/20/2019 | 11/20/2019 | P | PART |
Daryl Spivey
|
|
|
Please call Fernando at least 30 min prior to inspection, this is for above ground in wall rough in, waste/vent, domestic water and med gas. If I need to schedule these separately, please let Fernando know, Thank you so much! Phone #: ###-#### Inspection requested via web by Rhonda Marcum partial W/V and water and med gas marked on plans...........150 lb test on med gas ok........ds
|
Groundwork | 10/14/2019 | 10/14/2019 | 10/14/2019 | P | PASS |
Daryl Spivey
|
|
|
Please call Shane at least 30 min prior to inspection, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum g/w complete...........ds
|
Storm Drains | 10/8/2019 | 10/9/2019 | 10/9/2019 | A | PART |
Daryl Spivey
|
|
|
Please call Fernando at least 30 min prior to inspection, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum storm G/W tested ok............ds
|
Groundwork | 10/3/2019 | 10/4/2019 | 10/4/2019 | A | PART |
Daryl Spivey
|
|
|
Please call Fernando at least 30 min prior to inspection, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum marked on plan..........ds
|
Groundwork | 10/1/2019 | 10/2/2019 | 10/1/2019 | A | CANC |
Daryl Spivey
|
|
|
Please call Fernando at least 30 min prior to inspection, thank you. Phone #: ###-#### >> Inspection requested via web by Rhonda Marcum Inspection cancelled from web by: Rhonda Marcum
|
Groundwork | 9/26/2019 | 9/27/2019 | 9/27/2019 | P | PART |
Daryl Spivey
|
|
|
Please call Fernando at least 30 min prior to inspection, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum marked on plan...........ds
|
Water and/or Sewer | 9/24/2019 | 9/25/2019 | 9/25/2019 | A | CANC |
Daryl Spivey
|
|
|
Please call Fernando at least 30 min prior to inspection, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum
|
Groundwork | 9/25/2019 | 9/25/2019 | 9/25/2019 | A | PART |
Daryl Spivey
|
|
|
Please call Fernando at least 30 min prior to inspection, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum marked on plan ..........ds
|
Groundwork | 9/23/2019 | 9/24/2019 | 9/24/2019 | A | PART |
Daryl Spivey
|
|
|
Please call Fernando at least 30 min prior to inspection, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum marked on plan.......ds
|
Water and/or Sewer | 9/16/2019 | 9/17/2019 | 9/17/2019 | A | CANC |
Daryl Spivey
|
|
|
Please call Fernando at least 30 min prior to inspection, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum
|
Groundwork | 9/17/2019 | 9/17/2019 | 9/17/2019 | A | PART |
Daryl Spivey
|
|
|
Please call Fernando at least 30 min prior to inspection, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum marked plans........sanitary and rain drainage........ds
|
Groundwork | 9/5/2019 | 9/6/2019 | 9/6/2019 | A | PART |
Eric Strole
|
|
|
Please call Fernando at least 30 min prior to inspection, thank you. Phone #: ###-#### Inspection requested via web by Rhonda Marcum-Section complete is marked on plans.
|
Groundwork | 9/4/2019 | 9/4/2019 | 9/4/2019 | P | PART |
Eric Strole
|
|
|
Please contact Fernando 30 prior to arrival. Fernando: ###-####. Thank you. Phone #: ###-#### Inspection requested via web by Rhonda Marcum-Section complete is marked on plans.
|
Groundwork | 8/30/2019 | 8/30/2019 | 8/30/2019 | P | PART |
Daryl Spivey
|
|
|
Please call Fernando at least 30 min prior to inspection, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum partial sanitary marked on plan.........ds
|
Water and/or Sewer | 8/27/2019 | 8/28/2019 | 8/28/2019 | A | CANC |
Daryl Spivey
|
|
|
Please call Fernando at least 30 min prior to inspection, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum
|
Groundwork | 8/28/2019 | 8/28/2019 | 8/28/2019 | A | PART |
Daryl Spivey
|
|
|
Please call Fernando at least 30 min prior to inspection, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum partial sanitary line to outside bld......marked on plan...........ds
|
Groundwork | 8/26/2019 | 8/26/2019 | 8/26/2019 | P | PART |
Daryl Spivey
|
|
|
Please call Fernando at least 30 min prior to inspection, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum storm drain.......ds
|
Storm Drains | 8/21/2019 | 8/22/2019 | 8/22/2019 | A | PART |
Daryl Spivey
|
|
|
Please call Fernando at least 30 min prior to inspection, thank you. Phone #: ###-#### Inspection requested via web by Rhonda Marcum marked on plan...........ds
|
Groundwork | 8/22/2019 | 8/22/2019 | 8/22/2019 | A | PART |
Daryl Spivey
|
|
|
Partial sanitary marked on plan.......ds
|
Water and/or Sewer | 8/19/2019 | 8/20/2019 | 8/20/2019 | A | CANC |
Daryl Spivey
|
|
|
Please call Fernando at least 30 min prior to inspection, thank you. Phone #: ###-#### Inspection requested via web by Rhonda Marcum
|
Groundwork | 8/20/2019 | 8/20/2019 | 8/20/2019 | A | PART |
Daryl Spivey
|
|
|
Please call Fernando at least 30 min prior to inspection, thank you. Phone #: ###-#### Inspection requested via web by Rhonda Marcum roof drain partial ok...........ds
|
Water and/or Sewer | 8/15/2019 | 8/16/2019 | 8/16/2019 | A | CANC |
Daryl Spivey
|
|
|
Please call Fernando at ###-#### at least 30 min prior to inspection. Thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum
|
Groundwork | 8/16/2019 | 8/16/2019 | 8/16/2019 | P | PART |
Daryl Spivey
|
|
|
Please call Fernando at ###-#### at least 30 min prior to inspection. Thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum marked on plans............sanitary and roof drains.........ds
|
Water and/or Sewer | 8/1/2019 | 8/2/2019 | 8/2/2019 | P | CANC |
Daryl Spivey
|
|
|
Please call Fernando at ###-#### at least 30 min prior to inspection, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum
|
Groundwork | 8/2/2019 | 8/2/2019 | 8/2/2019 | P | PART |
Daryl Spivey
|
|
|
Please call Fernando at ###-#### at least 30 min prior to inspection, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum partial waste and roof drain ok......marked on plans........ds
|
Groundwork | 7/26/2019 | 7/29/2019 | 7/29/2019 | A | PART |
Daryl Spivey
|
|
|
Please call Fernando at least 30 min prior to inspection, thank you. Phone #: ###-#### Inspection requested via web by Rhonda Marcum marked on plans........ds
|
Groundwork | 7/22/2019 | 7/23/2019 | 7/23/2019 | A | PART |
Daryl Spivey
|
|
|
Froando Phone #: ###-#### marked on plans w/v...........ds
|
Issue PAID IN FULL permit | | | 6/20/2019 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 6/20/2019 | | DONE |
|
|
|
This permit was created on the web by Xenon Long
|