Information based on query as of Tuesday, May 21, 2024.
Permit Information
Permit NumberBLD12-01941
StatusFinaled
Name THE PROFESSIONALS
Site Address 405 S 8TH ST Unit: 175
Project NameFRESH OFF THE HOOK
Customer Number 
ePlanReviewNo
Description
(FRESH OFF THE HOOK – 8th St. Market Place – Ste# 175) This building is fire sprinklered for non-separated uses and area increase. Permit is to remodel an existing 1,750 square foot restaurant tenant space. This tenant space was last remodeled under BLD09-00074 for “Gandolfo’s Deli”. Work is to include: demolition of existing non-bearing partition walls, [construction of new non-bearing partition walls to create: a waiter prep area, an entry lobby, and a vestibule], relocate lighting, miscellaneous electrical, installation of a type I hood / grease duct, installation of new accessible doors / hardware, new hand wash sink, and interior finishes. . This building is fully Fire Sprinklered with an approved Fire Alarm system. Any alterations or modifications to the buildings Fire Sprinkler or Fire Alarm system WILL REQUIRE A SEPARATE PERMIT and shall be installed per NFPA 13 & NFPA 72 as regulated by the Boise Fire Department. **TLW**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Final12/12/201212/13/201212/13/2012APASS
DetailsDave Hannah
ron Phone #: ###-####
FIRE-Final Inspection12/12/201212/12/201212/12/2012PPASS
DetailsForrest France
Fire life safety final approved.
BLD-Final11/8/201211/9/201211/9/2012APART
DetailsDave Hannah
call for access - Ron Phone #: ###-#### ok for temp occ ok for perm occ after other trades go perm
FIRE-Final Inspection11/8/201211/8/201211/8/2012APART
DetailsForrest France
Temp. occupancy granted with R. Gervais approval until 12/15/12. Final pending modifications to the existing building fire alarm system to accomodate adequate visual coverage at two locations.
FIRE-Final Inspection11/2/201211/5/201211/5/2012APART
DetailsForrest France
Fire life safety final pending modifications to the existing fire alarm system. Adjustments to maintatin notification coverage will be necessary due to the new floorplan. Remainder of fire life safety conditions are satisfactory.
FIRE-Final Inspection10/29/201210/29/201210/29/2012PFAIL
DetailsForrest France
Type one hood failed to report to the FACP, modifications to the fire alarm system will be necessary to maintain coverage where new walls and partitions have been built, project related fire sprinkler permit needs called for inspection, noted one EM light to be repaired, relocate the K class PFE as discussed.
BLD-Framing/Rough-in9/5/20129/6/20129/6/2012APASS
DetailsDave Hannah
ron - call for access Phone #: ###-####