Permit Information
Permit NumberBLD12-02915
StatusFinaled
Name STEED CONSTRUCTION
Site Address 4017 W OVERLAND RD
Project NameBiomat Freezer Upgrade
Customer Number 
ePlanReviewNo
Description
(BIOMAT USA – Freezer expansion) Permit is to remodel an existing 11,548 sq. ft. office tenant space. This building is sprinklered for building area increase. Approval contingent upon adhering to the approved plans on file. Work to include: installation of new freezer wall panels (thermal barrier not required), installation of a new chain-link fence around new condensing unit, and interior finishes in accordance with Ch. 8 of the 2009 IBC. This building is fully Fire Sprinklered with an approved Fire Alarm system. Any alterations or modifications to the buildings Fire Sprinkler or Fire Alarm system WILL REQUIRE A SEPARATE PERMIT and shall be installed per NFPA 13 & NFPA 72 as regulated by the Boise Fire department. **TLW**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Final4/8/20134/9/20134/9/2013APASS
DetailsTom Arcoraci
Tim-PLease call prior to inspection Phone #: ###-####
DOC - Permit Finaled4/9/20134/9/20134/9/2013PPASS
DetailsTom Arcoraci
FIRE-Final Inspection4/8/20134/8/20134/8/2013PPASS
DetailsForrest France
Fire life safety final approved.
FIRE-Final Inspection4/4/20134/5/20134/5/2013PPASS
DetailsTroy Cobbley
Fire life safety passed
FIRE-Final Inspection2/20/20132/21/20132/21/2013AFAIL
DetailsForrest France
Modifications to the fire alarm system will be necessary due to remodel work (FIR permit required). Remainder of fire life safety inspection items passed.
BLD-Final2/20/20132/21/20132/21/2013ANR
DetailsTom Arcoraci
Tim-PLease call prior to inspection Phone #: ###-####
FIRE-Conference2/12/20132/12/20132/12/2013PDONE
DetailsTroy Cobbley
This entry is for future inspectors note. I noted the the existing ceiling mounted horn/strobe spacing appears to be blocked by the new freezer walls.