Information based on query as of Monday, May 20, 2024.
Permit Information
Permit NumberBLD16-02895
StatusFinaled
Name STEVE MCDERMOTTROE
Site Address 5150 W OVERLAND RD
Project NameIdaho Pizza at Hillcrest
Customer Number 
ePlanReviewYes
Description
(IDAHO PIZZA COMPANY – HILLCREST SHOPPING CENTER – PAD BUILDING) (5-1-17 PLAN MODIFICATION TO REVISE THE DRAWINGS TO SHOW THE ACTUAL ORIENTATION OF THE EXISTING ROOF JOISTS AND TO PROVIDE STRUCTURAL DETAILS TO REINFORCE ELEMENTS OF THE ROOF STRUCTURE TO SUPPORT ROOF TOP EQUIPMENT, STRUCTURAL DETAILS TO REINFORCE AROUND ROOF OPENINGS, AND STRUCTURAL DETAILS TO SUPPORT THE KITCHEN HOODS.) A fire sprinkler system will be installed in conjunction with this permit and will be used for occupancy. To convert a former 5,922 square foot retail sales building to a restaurant. Work is to include interior nonbearing walls, 2 restrooms accessible to the disabled, a new exterior door, exterior landing, exterior ramp, a grease hood (Type I) and grease duct system with 2 layers of duct wrap for allowed clearance reduction to combustible materials, a dishwashing hood (Type II) and duct, kitchen equipment, and interior finishes. Special Inspection is required for welding. The work is required to comply with the approved drawings, with the plan review report, with the structural design, and with all applicable codes and ordinances. The suspended ceiling grid is required to be maintained in compliance with the code in effect when it was installed (i.e. 1988 UBC). The fire sprinkler system is required to comply with NFPA 13 and the fire alarm system (no horns or strobes required) is required to comply with NFPA 72 as regulated by the Fire Department. Separate fire sprinkler permits and fire alarm permits shall be obtained prior to beginning any modification or installation work on such systems. **CJW**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Final7/5/20177/6/20177/6/2017APASS
DetailsJim Sly
Josh Phone #: ###-####
OK for Perm Occ.
BLD-Aging Inspection6/13/20176/13/20176/20/2017 PEND
DetailsJim Sly
BLD-Aging Inspection6/12/20176/12/20176/20/2017 PEND
DetailsJim Sly
BLD-Final4/24/20174/24/20174/24/2017PNR
DetailsJim Sly
Candy Phone #: ###-####
Owner to re-submit new Engineering for Equip. and Hood support.
BLD-Aging Inspection1/31/20171/31/20172/7/2017 PEND
DetailsJim Sly
WIP
BLD-Conference11/30/201611/30/201612/1/2016PDONE
DetailsJim Sly
Candy Phone #: ###-####
BLD-Final11/15/201611/16/201611/16/2016ANR
DetailsJim Sly
Cindy Phone #: ###-####
OK to final ........When Plumbing and Mech finals ......And structural verifies that support for large hood spans Min. 4 trusses.
BLD-Final10/28/201610/31/201610/31/2016APART
DetailsJim Sly
Candy Phone #: ###-####
OK for Temp Occ. OK for Perm Occ when Mech. and Plumb. signs off Perm.
FIRE-Final Inspection10/28/201610/31/201610/31/2016APASS
DetailsTroy Cobbley
Life safety passed
BLD-Final10/26/201610/26/201610/26/2016PNR
DetailsJim Sly
Candy Phone #: ###-####
Need Fire.......
FIRE-Final Inspection10/26/201610/26/201610/26/2016PCANC
DetailsTroy Cobbley
Not ready for a final yet due to project related fire alarm and fire sprinkler permits and corrections for life safety
BLD-Final10/25/201610/25/201610/25/2016PNR
DetailsJim Sly
Candy Phone #: ###-####
Temp on Plumb. Electr. and HVAC.......Complete fire corrections.
FIRE-Final Inspection10/25/201610/25/201610/25/2016PFAIL
DetailsTroy Cobbley
Inspection was actually for a conference. Multiple exit signs and emergency lights need repaired and or added. Need correct occupant load signs, need project related fire alarm and fire sprinkler permits finaled. Could not find a hood suppression permit.
BLD-Framing/Rough-in9/27/20169/27/20169/27/2016PPART
DetailsJim Sly
Candy would like a partial to cover inspection. Phone #: ###-####
OK to one side (rock) new walls. OK to rock both sides of walls with only electrical in them.