Permit Information
Permit NumberBLD17-01446
StatusFinaled
Name BUILDING RESOURCES INC
Site Address 3100 N LAKEHARBOR LN Unit: 175
Project NamePage One Power
Customer Number 
ePlanReviewYes
Description
(PAGE ONE POWER) **Permit is to remodel two existing office spaces into one 1,660 sq ft office. This permit is approved contingent upon adhering to the approved plans on file. Work to include: demo existing nonbearing interior walls, new light fixtures, new office walls, new interior doors, and new corridor wall constructed to maintain existing 1-hour rating. Interior finishes must be in compliance with Ch. 8 of the 2012 IBC. This building is fully Fire Sprinklered. Any alterations or modifications to the buildings Fire Sprinkler or Fire Alarm system WILL REQUIRE A SEPARATE PERMIT and shall be installed per NFPA 13 & NFPA 72 as regulated by the Boise Fire Department. **JAR*
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Final5/17/20185/18/20185/18/2018ADONE
DetailsTony Young
BLD-Aging Inspection5/11/20185/11/20185/17/2018 PEND
DetailsTony Young
BLD-Final5/15/20185/15/20185/16/2018PDONE
DetailsTony Young
BLD-Aging Inspection5/10/20185/10/20185/15/2018 PEND
DetailsTony Young
BLD-Final12/26/201712/27/201712/27/2017APASS
DetailsMike Jordan
Braven Phone #: ###-####. Ok for perm occ.
FIRE-Final Inspection12/22/201712/26/201712/26/2017APASS
DetailsJim Page
Fire sprinkler inspection complete, no fire alarm modifications, fire extinguishers are in place with current inspection tags. Final life fire safety inspection passed/complete.
FIRE-Final Inspection12/13/201712/14/201712/14/2017AFAIL
DetailsTroy Cobbley
Provide correct suite number, provide permit for sprinkler modifications (one pendant is too close to wall/contractor states Phoenix pulled permit for work), provide missing canopies, provide fire alarm permit for additional devices or demo, mount the fire extinguishers.

Braven Phone #: ###-####
BLD-Final12/13/201712/15/201712/14/2017ACANC
DetailsTony Young
Braven Phone #: ###-#### // cancelled per phone call from Braven 12/14/17 leg
BLD-Ceiling Grid Inspection12/7/201712/8/201712/8/2017PPASS
DetailsDave Hannah
late afternoon- Braven Phone #: ###-####
BLD-Wall cover11/21/201711/22/201711/22/2017PPART
DetailsTony Young
Braven Phone #: ###-####,, walls ok to cover
BLD-Framing/Rough-in11/16/201711/17/201711/17/2017APART
DetailsTony Young
after 10am please -Braven Phone #: ###-####,, main wall framing ok,, steel studs ok .vs wood,, needs more opposing top braces,, ok to start electrical work