Permit Information
Permit NumberBLD18-02610
StatusFinaled
Name STROTH GENERAL
Site Address 2645 W AIRPORT WAY
Project NameBest Western Vista Inn
Customer Number 
ePlanReviewYes
Description
(BEST WESTERN VISTA INN – EXTERIOR WORK) Permit is for adding parapet build ups at four existing exterior roof locations. Approval per approved plans on file, engineering design and design review approval DRH18-00308. Work to include: removal of select parapet cap, removal of select roof assembly and EIFS at new portions of built up parapet, removal of exterior neon lighting, select new section of built up parapet with bracing, new select EIFS and select new roof membrane at new parapet locations, new exterior paint, electrical work and new exterior light fixtures. This building is fully Fire Sprinklered with an approved Fire Alarm system. Any alterations or modifications to the buildings Fire Sprinkler or Fire Alarm system WILL REQUIRE A SEPARATE PERMIT and shall be installed per NFPA 13 & NFPA 72 as regulated by the Boise Fire Department. **JG**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Final8/7/20198/7/20198/7/2019APASS
DetailsJim Storey
contact Rick Phone #: ###-#### Inspection requested via web by rick pew
DOC - Permit Finaled8/7/20198/7/20198/7/2019PPASS
DetailsJim Storey
FIRE-Final Inspection7/26/20197/29/20197/29/2019PPASS
DetailsTroy Cobbley
Life safety passed. Concealed spaces have been filled with insulation

Insulators are to start at 12:00
if possible please come at end of day Phone #: ###-#### Inspection requested via web by rick pew
FIRE-Final Inspection7/9/20197/10/20197/10/2019AFAIL
DetailsTroy Cobbley
The new parapets have formed combustible concealed spaces as defined by NFPA 13 and need to be addressed as per NFPA 13. Per our conversation they will be filled with non-combustible insulation. This will need to be verified prior to a life safety sign off

contact Rick
have print and should be good to go Phone #: ###-#### Inspection requested via web by rick pew
FIRE-Final Inspection7/8/20197/9/20197/9/2019AFAIL
DetailsTroy Cobbley
No approved plans on site. Rick and I talked about possible fire sprinkler requirements in the new parapets.


contact Rick Pew at ###-#### Inspection requested via web by James Ressler
BLD-Final7/8/20197/8/20197/8/2019PNR
DetailsJim Storey
Please contact Rick ###-#### with any questions. Work completed on this project consisted of exterior paint and electrical lighting updates. Phone #: ###-#### Inspection need fire and zoning