BLD-Final | 8/11/2020 | 8/11/2020 | 8/11/2020 | P | PASS |
Jim Storey
|
|
|
card on site final ok
|
FIRE-Final Inspection | 8/11/2020 | 8/11/2020 | 8/11/2020 | P | PASS |
Troy Cobbley
|
|
|
Life safety passed. Racking permit finaled.
|
BLD-Final | 6/3/2020 | 6/3/2020 | 6/3/2020 | A | PART |
Jim Storey
|
|
|
final ok pending fire
|
FIRE-Final Inspection | 12/26/2018 | 12/27/2018 | 12/27/2018 | A | PART |
Jim Page
|
|
|
Previously noted items have been addressed, life fire safety inspection is complete, permit will remain in issued status until racking permit is issued.
Andy Phone #: ###-####
|
BLD-Final | 12/26/2018 | 12/27/2018 | 12/26/2018 | P | PART |
Jim Storey
|
|
|
Andy Phone #: ###-#### final ok pending racking permit and fire sign off.
|
FIRE-Final Inspection | 8/28/2018 | 8/28/2018 | 8/28/2018 | P | FAIL |
Jim Page
|
|
|
Remove plywood lid from northeast storage room or provide a fire sprinkler head to cover floor space in storage room. Fire alarm panel shows comm failure, communication from fire alarm panel to monitoring service is required before life fire safety inspection can be finaled.
Gene-pleae call with an approx meet time Phone #: ###-####
|