Information based on query as of Sunday, May 19, 2024.
Permit Information
Permit NumberBLD18-03381
StatusFinaled
Name DATUM CONSTRUCTION MANAGEMENT INC
Site Address 7048 W STATE ST
Project NameNorthgate - Workout Anytime
Customer NumberEARLY START BLD18-04479
ePlanReviewYes
Description
(NORTHGATE SHOPPING CENTER) (WORKOUT ANYTIME) (CZC18-00236) Permit for tenant improvements to an existing 7,015 sq ft retail space within the existing Northgate Shopping Center for a new fitness center. The building was previously a video rental store. Work to include: demo of interior non-structural partitions; minor exterior improvements to storefront; new interior non-bearing walls; exterior doors; restrooms and locker rooms with new plumbing; new ceiling; lighting and power; mechanical including new roof top unit and structural reinforcement of roof; and interior finishes in compliance with Ch. 8 of the 2015 IBC. The fire sprinkler system is used for building area increase and for fire area. Any alterations to the sprinkler system will require a separate permit and shall comply with NFPA 13 as regulated by the fire department. **JAR**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Final3/22/20193/22/20193/22/2019PPASS
DetailsTony Young
Fire Life Safety final requested.
Final Building inspection requested for late afternoon, after/during Fire Life Safety. Phone #: ###-#### Inspection requested via web by Greg Hedin
FIRE-Final Inspection3/22/20193/22/20193/22/2019PPASS
DetailsJim Page
Previously noted items have been corrected, final life fire safety inspection complete.

Fire Life Safety final requested. Phone #: ###-#### Inspection requested via web by Greg Hedin
BLD-Final3/14/20193/15/20193/15/2019ACANC
DetailsTony Young
Greg Phone #: ###-####
FIRE-Final Inspection3/14/20193/14/20193/14/2019PFAIL
DetailsJim Page
Mag lock access control needs to be integrated with the fire alarm system for door release under general water flow alarm. Ceiling fan on main floor needs to be integrated with the fire alarm panel to shut down on general water flow alarm per manufacture instructions. Provide emergency egress lighting for exit discharge as shown on city approved drawings. Verfiy CFM of newly installed HVAC unit, if unit moves more than 2000CFM then an in-duct smoke detector will be required for unit shutdown. Modifications to the fire alarm system requires a permit.

Greg Phone #: ###-####
BLD-Ceiling Grid Inspection3/5/20193/5/20193/5/2019PPASS
DetailsTony Young
Request ceiling grid inspection for cover, this afternoon. Phone #: ###-#### Inspection requested via web by Greg Hedin
BLD-Framing/Rough-in2/4/20192/5/20192/5/2019PPART
DetailsTony Young
request rough framing inspection for cover. Phone #: ###-#### Inspection requested via web by Greg Hedin,, walls ok