Permit Information
Permit NumberBLD19-00286
StatusFinaled
Name BEDSOLE CUSTOM HOMES INC
Site Address 2402 W JEFFERSON ST
Project NameSPARK MD
Customer Number 
ePlanReviewYes
Description
(SPARK MD) Permit is to remodel an existing 2,763 square foot medical clinic building with a 1,200 square foot basement. Approval contingent upon adhering to the approved plans on file. The new clinic will include 4 primary care rooms and 4 aesthetics rooms. The 8 rooms will be supported by a staff room, a blood draw station, and a break room for employees. Remodel is for the main level and no work to be done in the basement. Work to include: demolition of existing non-bearing walls, construction of new interior nonbearing walls, new doors, minor electrical work, minor mechanical work, minor plumbing work, and interior finishes in compliance with chapter 8 of the 2009 IBC. This building is not Fire Sprinklered. **JHB**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Final9/20/20199/20/20199/20/2019PPASS
DetailsBrandon Shaw
Caleb- Phone #: ###-####
DOC - Permit Finaled9/20/20199/20/20199/20/2019PPASS
DetailsBrandon Shaw
FIRE-Final Inspection9/17/20199/18/20199/18/2019APASS
DetailsJim Page
Previously noted items have been corrected, no fire sprinklers, no fire alarm modificaitons, fire extinguisher is placed with a current inspection tag, round type door hardware on breakroom door to be changed to lever type before building final, will be verified during final inspection. Final life fire safety inspection for area of work complete, signature card not provided, no signatures given.

Kaleb Phone #: ###-####
FIRE-Final Inspection9/16/20199/17/20199/17/2019ACANC
DetailsTroy Cobbley
Could not make it to this inspection due to work load and time constriants. Will need to be rescheduled. Caleb Phone #: ###-####
BLD-Final8/25/20198/26/20198/29/2019ACANC
DetailsDave Hannah
The building will be open after 9. Just ask for Becca. Thank you. Jay Phone #: ###-#### Inspection requested via web by Jay Bedsole
FIRE-Final Inspection8/27/20198/28/20198/28/2019AFAIL
DetailsJim Page
Provide code compliant door hardware for breakroom door. Provide a fire extinguisher with a current ispection tag, current tag is from 1986. Thumbturn deadbolt on main entry needs to be changed to a double-key deadbolt and provide signage at main door reading "Door to remain unlocked while building is occupied".

The building will be open at 9. Ask for Becca at the front desk. She has the approved plans. Thank you. Jay Phone #: ###-#### Inspection requested via web by Jay Bedsole
FIRE-Final Inspection8/26/20198/26/20198/26/2019PFAIL
DetailsTroy Cobbley
Left message on contacts voice mail that I was on the way. Got to project site but did not make contact with anyone except the owner. She did not have plans. No inspection performed. Jay Phone #: ###-####
BLD-Framing/Rough-in5/15/20195/15/20195/15/2019APASS
DetailsTony Young
Just inspection of the remaining rooms. Should be the front 2 rooms on the west side. The goal is to have the whole building approved for cover. Thank you. Jay Phone #: ###-#### Inspection requested via web by Jay Bedsole// ok after fixing the insulation
BLD-Framing/Rough-in5/9/20195/10/20195/10/2019APART
DetailsDave Hannah
Please give me a call. I would like an inspection on the rooms on the north side and the 3 rooms on the north west side, and the rooms in the center of the building. I have marked the plans with NO on the rooms that are not ready. The plans are on the table in the room on the south west corner of the building. Thank you. Jay Phone #: ###-#### Inspection requested via web by Jay Bedsole ok to cover rooms ok by elec
BLD-Framing/Rough-in4/25/20194/25/20194/25/2019PPART
DetailsBrandon Shaw
I need a rough in inspection on the east half of the building only. I'd like to hang sheet rock on that half only, so just an ok to cover the walls and ceiling on that half is the goal.
OK to cover as requested...