BLD-Final | 10/14/2019 | 10/15/2019 | 10/15/2019 | P | PART |
Dave Hannah
|
|
|
Dennis Phone #: ###-#### ok for tco ok to go perm after fire oks for permt
|
FIRE-Final Inspection | 10/14/2019 | 10/15/2019 | 10/15/2019 | A | PART |
Jim Page
|
|
|
Exit signage and emergency lighting that was noted on the past life safety inspections has been replaced and operational, sprinkler and fire alarm modifications are required due to the change in occupancy for area of work, fire alarm and fire sprinkler modifications are being designed and submitted for review. Partial final inspection for life fire safety is complete, fire exitnguisher is placed, inspection tag for fire exitguisher expired in september of 2019, fire extinguishers will need annual inspection performed before next final life fire safety inspection, annual inspection of fire extinguihsers will be verified at that time. Reccomend replacing the 2 fire sprinklers above dryers to a higher temp head, heads in place appear to be 165 degree heads. Per conversation with Ron Johnson with Boise Fire a 90 day TCO is authorized for life fire safety contingent upon fire sprinkler and fire alarm modifications being submitted, approved, inspected and passed. A follow up inspection will be required for life fire safety when the fire sprinkler and fire alarm modifications have been finaled.
Dennis Phone #: ###-####
|
FIRE-Final Inspection | 10/14/2019 | 10/14/2019 | 10/14/2019 | P | CANC |
Jim Page
|
|
|
Phone number provided for point of contact was not the correct phone number for Dennis, provide correct phone number for point of contact for proper coordination of inspection completion, this request is cancelled.
dennis Phone #: ###-####
|
FIRE-Final Inspection | 10/7/2019 | 10/7/2019 | 10/7/2019 | P | FAIL |
Troy Cobbley
|
|
|
Need the emergency dialer replacement permit, FIR19-00467, finaled first, need city approved plans and small documents, need tagged/mounted fire extinguisher, need exit signs in the room and the two paths of egress repaired, possibly need emergency lighting, sprinklers were spaced for the old light hazard conference room but now the room is an ordinary hazard Laundry room, the fire alarm strobes are overspaced from the northeast corner of the room.....ect.
Dennis Phone #: ###-####
|
BLD-Final | 10/7/2019 | 10/7/2019 | 10/7/2019 | P | CANC |
Dave Hannah
|
|
|
Dennis Phone #: ###-####
|
BLD-Final | 10/4/2019 | 10/7/2019 | 10/7/2019 | A | CANC |
Dave Hannah
|
|
|
Denise Phone #: ###-#### needs fire finals
|
BLD-Framing/Rough-in | 8/2/2019 | 8/2/2019 | 8/2/2019 | P | PASS |
Dave Hannah
|
|
|
Dennis Phone #: ###-####
|