BLD-Final | 5/27/2020 | 5/28/2020 | 5/28/2020 | A | PASS |
Brandon Shaw
|
|
|
screened // Paul Phone #: ###-####
|
DOC - Permit Finaled | 5/28/2020 | 5/28/2020 | 5/28/2020 | P | PASS |
Brandon Shaw
|
|
|
|
BLD-Final | 5/14/2020 | 5/15/2020 | 5/15/2020 | P | PART |
Mike Jordan
|
|
|
Paul Phone #: ###-####. Ok for temp occ. Needs to provide ADA POS.
|
FIRE-Final Inspection | 5/13/2020 | 5/14/2020 | 5/14/2020 | A | PASS |
Jim Page
|
|
|
Previously noted items have been corrected, curtian that was causing fire sprinkler blockage has been removed, no fire sprinkler modifications, no fire alarm modifications, fire extinguishers are in common areas with current inspection tags. Final life fire safety inspection is complete, signatures provided on permit sign off card.
Paul *screened* Phone #: ###-####
|
FIRE-Final Inspection | 3/9/2020 | 3/10/2020 | 3/10/2020 | A | FAIL |
Jim Page
|
|
|
Fire sprinkler modifications are required in area of work, fire sprinkler modifications will reuqire a seperate permit. Entry door hardware does not comply with 1010.1.9.1 of the 2015 International Fire Code. Provide annual inspection on fire extinguishers and wall mount fire extinguishers as discussed, extinguishers are not to be placed on the floor per code requirements, extinguisher must be mounted, not less than 4 inches off of the floor and not more than 48 inches to extinguisher mechanism.
Paul- please call for access Phone #: ###-####
|
FIRE-Final Inspection | 3/4/2020 | 3/6/2020 | 3/6/2020 | A | FAIL |
Jim Page
|
|
|
Could not access space due to being locked, provide code compliant door hardware on main entry.
Paul Phone #: ###-####
|
BLD-Final | 3/2/2020 | 3/4/2020 | 3/4/2020 | A | NR |
Brandon Shaw
|
|
|
Need Fire/life...
|