Permit Information
Permit NumberBLD19-04623
StatusFinaled
Name PERIGEE GROUP LLC
Site Address 1488 S EAGLE FLIGHT WAY
Project NameGuardian Home Care, INC
Customer Number 
ePlanReviewYes
Description
(GUARDIAN HOME CARE, INC) Permit is to remodel an existing 2,552 sq. ft. tenant space. Approval is contingent upon adhering to the approved plans on file. Work to include: removal of select interior nonbearing walls, removal of select door/door frames and relocate, removal of select floor finish, construction of select new interior non-bearing walls, select new wall infill, select new door/door frames, select new interior windows, millwork, select new floor finish, electrical work and interior finishes in compliance with Ch. 8 of the current IBC. This building is fire sprinklered for use flexibility, any alterations or modifications to the buildings Fire Sprinkler or Fire Alarm system WILL REQUIRE A SEPARATE PERMIT and shall be installed per NFPA 13 & NFPA 72 as regulated by the Boise Fire Department. **JG**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Final2/17/20202/18/20202/18/2020APASS
DetailsMike Jordan
Phone #: ###-#### Inspection requested via web by Travis Knutson. Ok for perm occ.
BLD-Final1/31/20201/31/20201/31/2020PPEND
DetailsMike Jordan
Please call Dustin 208.960.2778 30 min prior to arrival. We have three inspections today, Fire Alarm, Fire Life Safety, and Building Final. Phone #: ###-#### Inspection requested via web by Travis Knutson. Will be ok for perm occ. once mechanical permit issues have been resolved.
FIRE-Final Inspection1/31/20201/31/20201/31/2020PPASS
DetailsTroy Cobbley
Life safety passed. Please call Dustin 208.960.2778 30 min prior to arrival. We have three inspections today, Fire Alarm, Fire Life Safety, and Building Final. Phone #: ###-#### Inspection requested via web by Travis Knutson
FIRE-Conference1/28/20201/28/20201/28/2020ADONE
DetailsJim Page
Noted that the fire sprinkler head in Room 100 Lobby as shown on city approved drawings has a substantial amount of "Loading" as specified by NFPA25, chapter 5. Sprinkler head cannot be cleaned, per NFPA25 sprinkler head will need to be replaced, sprinkler head replacement needs to be accomplished before life fire safety inspection, life fire safety inspection will result in a fail if sprinkler head is cleaned or not replaced.
BLD-Framing/Rough-in12/20/201912/20/201912/20/2019PPASS
DetailsMike Jordan
Antonio Phone #: ###-####
BLD-Framing/Rough-in12/19/201912/20/201912/20/2019AFAIL
DetailsMike Jordan
Please call 20min prior to inspection Phone #: ###-#### Inspection requested via web by Travis Knutson. repairs not completed.
BLD-Framing/Rough-in12/19/201912/19/201912/19/2019PFAIL
DetailsMike Jordan
Phone #: ###-#### Inspection requested via web by Travis Knutson. Needs to remove screws from top plate to grid and install supports to structure above.
BLD-Framing/Rough-in12/16/201912/17/201912/17/2019ACANC
DetailsMike Jordan
Phone #: ###-#### Inspection requested via web by Travis Knutson. Cancelled, no approved plans.