Final | 12/11/2014 | 12/11/2014 | 12/11/2014 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by daniel bibikov Final ok
|
Final | 12/10/2014 | 12/10/2014 | 12/10/2014 | A | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by daniel bibikov 406.4(B)- Recepticals that have ground contacts shall be connected to equiptment ground. 410.16(C)(1)- Surface mounted fixtur shall clear shelf be minimum of 12" if incondescent lamps can be installed.
|
Rough-In Permanent Service | 10/15/2014 | 10/15/2014 | 10/15/2014 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by daniel bibikov Rough in ok cover p/s u/g n ok 5 Meters
|